Technical manual of iPACS-5762A-G bus tie (segmental) protection and monitoring device
The Wiscom iPACS-5762A-G is a bus tie (segmental) protection and monitoring device designed for 35kV bus tie or incoming switch charging protection and monitoring. It supports panel mounting or local installation in switchgear.
The device provides charging overcurrent protection (two stages), zero-sequence current protection, independent operation circuits, 15 customizable remote signaling inputs, one group of breaker remote control, extensive telemetry measurements, event recording, and supports DL/T667-1999 (IEC60870-5-103) and Ethernet communication. This manual is written in Chinese.
| Operating temperature | -25℃ to +60℃ |
|---|---|
| Rated DC voltage | 110V (±15%/-20%) |
| Rated AC voltage | 57.7V phase, 100V line |
| Rated AC current | 5A, 1A |
| Rated frequency | 50Hz |
| AC voltage burden | <0.5VA per phase |
| AC current burden (5A) | <1.0VA per phase |
| AC current burden (1A) | <0.5VA per phase |
| DC power consumption (normal) | <15W |
| AC voltage overload continuous | 1.2x rated |
| AC voltage overload 10s | 1.4x rated |
| AC current overload continuous | 2x rated |
| AC current overload 10s | 10x rated |
| AC current overload 1s | 40x rated |
| Charging overcurrent setting range | 0.1In to 20In |
| Charging overcurrent setting error | <5% |
| Zero-sequence current setting range | 0.02A to 12A (external) |
| Remote signaling resolution | <1ms |
| Remote signaling input type | Passive contact |
| Signal contact capacity | 5A continuous, 0.3A breaking (DC110V) |
| Auxiliary relay contact capacity | 5A continuous, 0.2A breaking (DC110V) |
| Trip contact capacity | 5A continuous, 0.3A breaking (DC110V) |
It supports DL/T667-1999 (IEC60870-5-103) and Ethernet (100Mbps) communication.
Rated DC voltage 110V, AC voltage 57.7V phase / 100V line, AC current 5A or 1A.
Charging overcurrent protection (two stages) and zero-sequence current protection.
-25°C to +60°C.