Wiscom iPACS-5762A-G Bus Tie (Segmental) Protection and Monitoring Device Technical Manual

Technical manual of iPACS-5762A-G bus tie (segmental) protection and monitoring device


Wiscom iPACS-5762A-G Bus Tie (Segmental) Protection and Monitoring Device Technical Manual - cover page
Brand
Wiscom
Category
Monitoring Equipment
Document type
User Manual
Language
Chinese
Pages
19
File format
PDF
File size
776 KB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
75BA13031B7157EF476AF9F14C9E7407

About this manual

The Wiscom iPACS-5762A-G is a bus tie (segmental) protection and monitoring device designed for 35kV bus tie or incoming switch charging protection and monitoring. It supports panel mounting or local installation in switchgear.

The device provides charging overcurrent protection (two stages), zero-sequence current protection, independent operation circuits, 15 customizable remote signaling inputs, one group of breaker remote control, extensive telemetry measurements, event recording, and supports DL/T667-1999 (IEC60870-5-103) and Ethernet communication. This manual is written in Chinese.

What's inside

  • Overview
  • Technical Parameters
  • Software Working Principle
  • Setting Contents and Calibration
  • Device Wiring Terminals and Description
  • Protection Configuration and Functions
  • Measurement and Control Functions
  • Protection Information Functions
  • Device Self-Check and Alarms
  • Time Synchronization

Specifications

Operating temperature-25℃ to +60℃
Rated DC voltage110V (±15%/-20%)
Rated AC voltage57.7V phase, 100V line
Rated AC current5A, 1A
Rated frequency50Hz
AC voltage burden<0.5VA per phase
AC current burden (5A)<1.0VA per phase
AC current burden (1A)<0.5VA per phase
DC power consumption (normal)<15W
AC voltage overload continuous1.2x rated
AC voltage overload 10s1.4x rated
AC current overload continuous2x rated
AC current overload 10s10x rated
AC current overload 1s40x rated
Charging overcurrent setting range0.1In to 20In
Charging overcurrent setting error<5%
Zero-sequence current setting range0.02A to 12A (external)
Remote signaling resolution<1ms
Remote signaling input typePassive contact
Signal contact capacity5A continuous, 0.3A breaking (DC110V)
Auxiliary relay contact capacity5A continuous, 0.2A breaking (DC110V)
Trip contact capacity5A continuous, 0.3A breaking (DC110V)

Frequently asked questions

What communication protocols does the device support?

It supports DL/T667-1999 (IEC60870-5-103) and Ethernet (100Mbps) communication.

What are the rated voltage and current inputs?

Rated DC voltage 110V, AC voltage 57.7V phase / 100V line, AC current 5A or 1A.

What protection functions are included?

Charging overcurrent protection (two stages) and zero-sequence current protection.

What is the operating temperature range?

-25°C to +60°C.