WISCOM iPACS-5792P Protection Information Substation Technical Manual

The iPACS-5792P protection information substation adopts a safe operating system, a fanless and rotating部件hardware design, and a high-performance dual-core CPU Intel(R) Celeron(R) 2980U with a frequency of 1.69G, 4G memory, and 128G solid state hard drive.


WISCOM iPACS-5792P Protection Information Substation Technical Manual - cover page
Brand
Wiscom
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
11
File format
PDF
File size
561 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
B07C8C7E47F37298318E7FC4EFEAF58F

About this manual

This technical manual describes the iPACS-5792P protection information substation from WISCOM SYSTEM CO., LTD (Jiangsu Jinzhi Technology). The device is a sub-station of a relay protection fault information processing system, intended for intelligent and conventional substations up to 1000 kV as well as power plants, hydro plants and switch stations. It collects action signals, alarm information, fault reports, settings and disturbance records from protection devices and fault recorders, displays the information locally, and transmits data to remote master stations over multiple communication protocols.

The manual lists the device's technical parameters (electrical, type-test, communication interface and gateway performance requirements), describes the hardware module structure including the CPU, serial, serial-fiber, GPS and dual-machine interface plugins, explains front-panel indicator lights and the recommended inspection cycle, and closes with a network and information security statement covering security audit, software fault tolerance, the MD5 encryption algorithm and active ports. This manual is written in Chinese.

What's inside

  • Overview (scope and main functions)
  • Technical parameters
  • Type test parameters
  • Communication interface parameters
  • Hardware structure
  • Structure view and installation dimensions
  • Operation and maintenance (indicator lights, inspection cycle)
  • Network and information security statement

Specifications

Operating temperature-20°C to +55°C
Storage temperature-40°C to +70°C
Relative humidity5% to 95%, non-condensing
Rated supply voltageDC110V, DC220V, AC220V
Power consumption< 45 W per unit
Memory4 GB DDR2
Storage128 GB SATA SSD
Ethernet ports12 RJ45 ports, 100 Mbit/s, IEC 61850
Time synchronizationSecond/minute pulse and IRIG-B via RS-485
Other interfaces4 USB ports, 1 VGA port
Device capacitySupports at least 255 connected devices
SOE buffer≥ 8000 entries per channel
Time sync accuracyIRIG-B ≤ 1 ms, SNTP ≤ 100 ms
MTBF≥ 30000 h

Frequently asked questions

What supply voltages does the iPACS-5792P accept?

The device accepts DC110V, DC220V or AC220V rated voltage, with an input range of 80% to 120% of the rated voltage.

How often should the device be inspected?

The theoretical inspection cycle is 15 working days, but to guard against unexpected events it is recommended that operating personnel inspect the device once a week.

What do the alarm and time-sync indicator lights mean?

The red alarm light stays on when a hardware, software or configuration fault occurs and is off during normal operation; the red IRIG-B time-sync abnormal light stays on when the time synchronization service is abnormal.

Which network ports are active on the device?

Active ports are 22 (SSH), 102 (61850 MMS), 2007 and 7007 (database server services) and 2404 (103/104 upstream service).

Download PDF (561 KB)

More Wiscom Manuals


View all Wiscom manuals →