The iPACS-5792P protection information substation adopts a safe operating system, a fanless and rotating部件hardware design, and a high-performance dual-core CPU Intel(R) Celeron(R) 2980U with a frequency of 1.69G, 4G memory, and 128G solid state hard drive.
This technical manual describes the iPACS-5792P protection information substation from WISCOM SYSTEM CO., LTD (Jiangsu Jinzhi Technology). The device is a sub-station of a relay protection fault information processing system, intended for intelligent and conventional substations up to 1000 kV as well as power plants, hydro plants and switch stations. It collects action signals, alarm information, fault reports, settings and disturbance records from protection devices and fault recorders, displays the information locally, and transmits data to remote master stations over multiple communication protocols.
The manual lists the device's technical parameters (electrical, type-test, communication interface and gateway performance requirements), describes the hardware module structure including the CPU, serial, serial-fiber, GPS and dual-machine interface plugins, explains front-panel indicator lights and the recommended inspection cycle, and closes with a network and information security statement covering security audit, software fault tolerance, the MD5 encryption algorithm and active ports. This manual is written in Chinese.
| Operating temperature | -20°C to +55°C |
|---|---|
| Storage temperature | -40°C to +70°C |
| Relative humidity | 5% to 95%, non-condensing |
| Rated supply voltage | DC110V, DC220V, AC220V |
| Power consumption | < 45 W per unit |
| Memory | 4 GB DDR2 |
| Storage | 128 GB SATA SSD |
| Ethernet ports | 12 RJ45 ports, 100 Mbit/s, IEC 61850 |
| Time synchronization | Second/minute pulse and IRIG-B via RS-485 |
| Other interfaces | 4 USB ports, 1 VGA port |
| Device capacity | Supports at least 255 connected devices |
| SOE buffer | ≥ 8000 entries per channel |
| Time sync accuracy | IRIG-B ≤ 1 ms, SNTP ≤ 100 ms |
| MTBF | ≥ 30000 h |
The device accepts DC110V, DC220V or AC220V rated voltage, with an input range of 80% to 120% of the rated voltage.
The theoretical inspection cycle is 15 working days, but to guard against unexpected events it is recommended that operating personnel inspect the device once a week.
The red alarm light stays on when a hardware, software or configuration fault occurs and is off during normal operation; the red IRIG-B time-sync abnormal light stays on when the time synchronization service is abnormal.
Active ports are 22 (SSH), 102 (61850 MMS), 2007 and 7007 (database server services) and 2404 (103/104 upstream service).