WXH-872 Microcomputer Line Protection and Control Device is a new type of microcomputer protection device, which adopts advanced microcomputer technology and digital signal processing technology. It has the advantages of complete protection functions, high measurement accuracy, good reliability and strong anti-interference ability. The device is suitable for the protection of distribution lines with voltage levels of 10kV and below, and can also be used for the protection of distribution lines with voltage levels of 35kV and below.
XJ Electric WXH-872 is a microcomputer line protection and control device for feeder protection in 3-10 kV substation distribution stations. It is equipped with three-stage overcurrent protection, zero-sequence overcurrent protection, acceleration protection, reclosing, overload protection, underfrequency load shedding, and loss-of-voltage protection, along with measurement, telemetry, tele-signaling, and telecontrol functions.
The technical manual describes the device's protection configuration, technical specifications, settings, hardware, operation, debugging, and ordering information. Its rated AC current is 5 A, rated frequency is 50 Hz, and rated DC power supply is DC220 V or DC110 V. This manual is written in Chinese.
| Rated AC voltage | Phase voltage 100/sqrt(3) V |
|---|---|
| Rated AC current | 5 A |
| Zero-sequence current | 1 A |
| Rated frequency | 50 Hz |
| Rated DC power supply | DC220 V or DC110 V; allowable range 80%-115% |
| AC current circuit power consumption | Not more than 1 VA per phase; zero-sequence current circuit not more than 0.3 VA |
| Measurement AC current circuit power consumption | Not more than 0.75 VA per phase |
| AC voltage circuit power consumption | Not more than 0.5 VA per phase |
| DC circuit power consumption | Not more than 12 W in normal operation; not more than 15 W during protection operation |
| AC current overload capability | 2 times rated current continuous; 50 times rated current for 1 s |
| AC voltage overload capability | 1.2 times rated voltage continuous; 1.4 times rated voltage for 10 s |
| Setting range, AC voltage | 10 V to 100 V |
| Setting range, AC current | 0.1 In to 20 In |
| Setting range, time delay | 0 s to 600 s |
| Setting range, frequency | 45 Hz to 49.5 Hz |
| Setting range, slip | 0.5 Hz/s to 10 Hz/s |
| Setting error, current | Less than +/-5% or +/-0.01 In |
| Setting error, voltage | Less than +/-5% or +/-0.25 V |
| Setting error, frequency | Less than +/-0.02 Hz |
| Setting error, slip | Less than +/-10% or +/-0.2 Hz/s |
| Time-delay error | Average error not more than +/-2% of setting or +/-40 ms |
| Current measurement accuracy | +/-0.5% |
| Voltage measurement accuracy | +/-0.5% |
| Frequency measurement accuracy | +/-0.01 Hz |
| Power measurement accuracy | +/-0.5% for P, Q, S, and power factor |
| Remote signaling input | DC24 V input with optoelectronic isolation; SOE resolution not more than 1 ms |
| Fault event report capacity | At least 100 fault event reports and 20 fault waveforms |
| Normal waveform record | 4 cycles before fault and 6 cycles after fault, 10 cycles total |
| Event record capacity | 100 event records and self-check reports |
| Trip/close contact capacity | 50 W break; long-term current not more than 10 A at not more than 250 V, not more than 1 A, L/R 5 ms +/-0.75 ms |
| Signal/other contact capacity | 20 W break; long-term current not more than 5 A at not more than 250 V, not more than 0.5 A, L/R 5 ms +/-0.75 ms |
| Insulation resistance | Not less than 100 Mohm |
| Operating temperature | -25 deg C to +55 deg C |
| Storage temperature | -25 deg C to +55 deg C |
| Transport temperature | -40 deg C to +70 deg C |
| Atmospheric pressure | 86 kPa to 106 kPa |
| Relative humidity | 5% to 95% (no condensation or icing inside the product) |
| Communication interfaces | 1 RS485 serial port and 1 Ethernet port; DL/T 860 series standard |
| GPS time synchronization pulse interface | 1 |
It is used for feeder protection in 3-10 kV substation distribution stations.
The rated AC current is 5 A.
It provides one RS485 serial port and one Ethernet port using the DL/T 860 series standard.
The operating temperature range is -25 deg C to +55 deg C.