XJ Electric FCK-831A Microcomputer Measurement and Control Device User Manual

The FCK-831A Microcomputer Measurement and Control Device is a measuring, controlling, monitoring, recording, and synchronization unit developed for the interval layer of substation automation systems with a voltage level of 35kV to 110kV. It supports the IEC 60870-5-104/IEC 61850 protocol.


XJ Electric FCK-831A Microcomputer Measurement and Control Device User Manual - cover page
Brand
XJ Electric
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
24
File format
PDF
File size
345 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
7B4A1B8F766E63B1D18307C7C7F305C1

About this manual

The XJ Electric FCK-831A is a microcomputer measurement and control device designed for automation systems in substations with voltage levels between 35kV and 110kV. It functions as an interval layer measurement and control unit, supporting measurement, control, monitoring, recording, and synchronization capabilities. The device supports IEC 60870-5-104 and IEC 61850 communication protocols. This manual is written in Chinese.

What's inside

  • Overview
  • Main Functional Features
  • Main Technical Indicators
  • Basic Functions
  • Optional Functions
  • Device Hardware Structure
  • Plug-in Module Introduction
  • Adjustment Value Table
  • Human-Machine Interface
  • Commissioning and Maintenance

Specifications

Voltage RangeAC 57.7 V or 100 V, 50 Hz
Current RangeAC 5 A or 1 A, 50 Hz
Frequency Range45 Hz~55 Hz
Power Measurement Accuracy±0.5%
DC Input Range0 V~+5 V
Control Output Capacity (DC)30 V, 5 A
Control Output Capacity (AC)220 V, 5 A
Operating Temperature-25 ℃~+55 ℃
Power Supply (AC)220 V
Power Supply (DC)110 V or 220 V

Frequently asked questions

What voltage levels is the FCK-831A designed for?

The device is primarily developed for automation systems in substations with voltage levels between 35kV and 110kV.

What communication protocols does the device support?

The device supports IEC 60870-5-104 and IEC 61850 protocols.

How many records can the device store?

The device can store a maximum of 100 records, including tele-signal, event, alarm, and operation records.

What is the accuracy of the frequency measurement?

The frequency measurement accuracy is ±0.02 Hz using software frequency measurement.