The VT1000 is a vibration transmitter that converts vibration signals into 4-20mA current signals or 0-10V voltage signals. It features: 1. High accuracy: The VT1000 has an accuracy of ±1%, making it ideal for applications requiring high-precision measurements. 2. High stability: The VT1000 has excellent stability, making it ideal for applications requiring long-term stable operation. 3. High reliability: The VT1000 has a very high reliability, making it ideal for applications requiring high-reliability operation.
The VIBTransmitter VT1000 from EC Systems is a universal module for condition monitoring of rotating machinery with constant and variable rotational speed. It accepts an ICP (IEPE) standard accelerometer input and provides a 4..20 mA output proportional to the signal estimate, plus a built-in connector for the AC voltage signal from the vibration sensor (10 Vpp). Measurement can be set to vibration velocity or acceleration, with RMS or PEAK estimates.
This user manual describes the module, its front panel indicators and connectors, mounting on a 35 mm DIN rail, galvanic isolation, the AC voltage output, activation after power-up, and measurement parameter configuration using switch sets SW1 and SW2. It ends with the technical parameters of the module and the manufacturer's contact address.
| Power supply | 24 VDC (18..36 VDC) |
|---|---|
| Power consumption | <4 W |
| Sensor type | IEPE, 100 mV/g, 4.7 mA @ 20 V |
| Measured values | velocity, acceleration |
| Types of estimates | RMS, 0-PEAK |
| Low-pass filter | 1/10 kHz, 24 dB/oct., 4th order |
| High-pass filter | 3/10 Hz, 12 dB/oct., 2nd order |
| Isolation | 1 kVDC (2 or 3 kVDC optionally) |
| Current output | 2 or 3 wired 4..20 mA current loop |
| Voltage output | AC, 10 Vpp max. |
| Operating temperature | -20..+60°C |
| Operating relative humidity | <95% RH |
| Protection class | IP40 |
| Dimensions | 23 x 100 x 120 mm (W x H x L) |
| Weight | 150 g |
| Mounting | 35 mm DIN rail |
It has an ICP (IEPE) standard accelerometer input, specified as IEPE, 100 mV/g, 4.7 mA @ 20 V.
The module is designed for mounting on a 35 mm DIN rail in an upright position.
It provides a 4..20 mA current loop output proportional to the signal estimate and an AC voltage output of 10 Vpp max.
After connecting the power the module enters a testing procedure and all LEDs flash briefly; if everything is operating properly, an LED then pulses at approximately 1 Hz.
The switches should be set up on a switched-off device; if the setup was done on an operating module, it must be restarted to activate the new configuration.