This manual describes the operation of the DSE705 ATS control module.
This is the operating manual (issue 1.1, document 057-043) for the Deep Sea Electronics DSE705, a configurable Automatic Transfer Switch control module designed to work with generator control modules that accept a remote start input. The module monitors the incoming AC mains supply on one or three phases for under voltage, starts the generating set when the supply falls out of limits, and controls the transfer devices to move the load between mains and generator.
The manual describes manual run on load and run off load operation, the automatic mode sequence with its start, mains return, warm up and cooling timers, and the front-panel configuration procedure with its LED codes. Configuration tables list the available settings for timers, remote start input type and function, auxiliary outputs and mains under-voltage trip/return levels, followed by terminal descriptions, specification, solid state outputs, dimensions and typical connections.
| Mains supply monitored | 1 or 3 phases |
|---|---|
| Alternator frequency for warm up | 45 Hz |
| Generator fail threshold | Frequency falls below 20 Hz |
| Start Delay timer range | 0 to 180 seconds, selectable |
| Mains under voltage trip / return settings | 60V / 70V up to 180V / 200V |
| Configuration method | Front panel, no computer or programming lead required |
Configuration is done from the front panel once Configuration Mode is selected with a small switch on the rear left-hand edge of the PCB; no computer or programming lead is needed.
The Mains Fail Delay timer is initiated, after which the Start/Run output is activated, and once the alternator reaches 45 Hz the Warm Up timer runs before the load is transferred to the generator.
When the input is activated, the switching device that is closed is opened for load shedding and is not re-closed until the input is removed.
If the generator frequency falls below 20 Hz the unit switches back to the mains, even if the mains is not available.