Deep Sea Electronics DSE705 ATS Control Module Operating Manual

This manual describes the operation of the DSE705 ATS control module.


Deep Sea Electronics DSE705 ATS Control Module Operating Manual - cover page
Brand
DEEP SEA ELECTRONICS
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
13
File format
PDF
File size
167 KB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
32C66FD2A9DA546F2B92D2E39B7CAC37

About this manual

This is the operating manual (issue 1.1, document 057-043) for the Deep Sea Electronics DSE705, a configurable Automatic Transfer Switch control module designed to work with generator control modules that accept a remote start input. The module monitors the incoming AC mains supply on one or three phases for under voltage, starts the generating set when the supply falls out of limits, and controls the transfer devices to move the load between mains and generator.

The manual describes manual run on load and run off load operation, the automatic mode sequence with its start, mains return, warm up and cooling timers, and the front-panel configuration procedure with its LED codes. Configuration tables list the available settings for timers, remote start input type and function, auxiliary outputs and mains under-voltage trip/return levels, followed by terminal descriptions, specification, solid state outputs, dimensions and typical connections.

What's inside

  • Introduction
  • Description of Operation
  • Manual Run On Load
  • Manual Run Off Load
  • Automatic Mode of Operation
  • Configuration Instructions
  • Configuration Tables
  • Terminal Description
  • Specification
  • Solid State Outputs

Specifications

Mains supply monitored1 or 3 phases
Alternator frequency for warm up45 Hz
Generator fail thresholdFrequency falls below 20 Hz
Start Delay timer range0 to 180 seconds, selectable
Mains under voltage trip / return settings60V / 70V up to 180V / 200V
Configuration methodFront panel, no computer or programming lead required

Frequently asked questions

How is the DSE705 configured?

Configuration is done from the front panel once Configuration Mode is selected with a small switch on the rear left-hand edge of the PCB; no computer or programming lead is needed.

What happens in automatic mode when the mains supply fails?

The Mains Fail Delay timer is initiated, after which the Start/Run output is activated, and once the alternator reaches 45 Hz the Warm Up timer runs before the load is transferred to the generator.

What does the Close To Neutral Position input do?

When the input is activated, the switching device that is closed is opened for load shedding and is not re-closed until the input is removed.

What happens if the generator fails while running?

If the generator frequency falls below 20 Hz the unit switches back to the mains, even if the mains is not available.