This manual provides installation, operation, and maintenance instructions for the DSE4510 Autostart and DSE4520 Automatic Mains Failure PLC modules.
The DSE4510 and DSE4520 modules are part of the DSEGenset® range, designed to provide differing levels of functionality across a common platform. The DSE4510 acts as an Autostart Module, allowing the operator to start and stop the generator and transfer the load automatically. The DSE4520 adds Automatic Mains Failure functionality, automatically starting and stopping the generator set based on the status of the mains (utility) supply. Both modules feature an icon-based LCD display, True RMS Voltage and Current monitoring (on specific variants), USB communications, and engine parameter monitoring via an ARM microprocessor.
| Minimum supply voltage | 8V continuous |
|---|---|
| Maximum supply voltage | 35V continuous |
| Maximum operating current (12V) | 85mA |
| Measurement type | True RMS conversion |
| Sample Rate | 5KHz or better |
| Minimum frequency | 3.5Hz |
| Maximum frequency | 75.0Hz |
The DSE4510 is an Autostart Module that allows the operator to start and stop the generator and transfer the load automatically.
Any future updates of this document will be included on the DSE website at www.deepseaplc.com.