The EchoPod® Quick Start provides basic mounting, setup and use instructions for getting the EchoPod® up and running quickly.
Flowline EchoPod UG01 and UG03 series quick start provides basic mounting, setup, and use instructions for the ultrasonic liquid level switch, controller, and transmitter. It lists components such as a 4 ft (1.2 m) cable, Viton gasket, and optional USB key fob, and describes configuration through WebCal software before mounting.
The guide covers tank measurement, dimensional entry, tank level confirmation, writing configuration to the unit, mounting options and guidelines, stand-pipe installation, and wiring. It includes relay and power wiring notes, safety guidance, and common wiring examples for displays, controllers, and PLCs.
| Cable length | 4 ft (1.2 m) |
|---|---|
| Viton gasket | 2 in, P/N 210138 (G version only) |
| USB key fob | P/N LI99-2001 (included with some models) |
| Maximum computer-to-sensor distance during configuration | 15 ft |
| Red and black wire extension | Up to 1,000 ft with 22-gauge or larger wire |
| Green and white wire extension | Do not extend beyond 15 ft |
| Supply voltage | Never exceed 28 VDC |
| Relay power | Do not exceed 28 VDC |
| Mounting distance from side wall | At least 2 in |
| 2 in diameter riser height | No taller than 4 in |
| Larger diameter riser height | No taller than 12 in |
| Riser height-to-diameter ratio | 2:1 |
| Stand-pipe minimum diameter | 2 in |
| Stand-pipe bottom cut | 45 degrees |
| Pressure equalization hole | 1/4 in |
| Relay type | Latching relays |
EchoPod is configured through WebCal, a PC software program.
Depending on part number and configuration, EchoPod comes with a 4 ft cable, Viton gasket, Quick Start, and some models include a USB key fob.
The maximum distance is 15 feet.
Supply voltage should never exceed 28 VDC.