Flowline EchoPod UG01 & UG03 Series Ultrasonic Liquid Level Switch, Controller & Transmitter Quick Start

The EchoPod® Quick Start provides basic mounting, setup and use instructions for getting the EchoPod® up and running quickly.


Flowline EchoPod UG01 & UG03 Series Ultrasonic Liquid Level Switch, Controller & Transmitter Quick Start - cover page
Brand
FlowLine
Category
Monitoring Equipment
Document type
Quick Start Guide
Language
English
Pages
12
File format
PDF
File size
1.5 MB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
5965A7BAD3D81E22BD450B074EE8DC3B

About this manual

Flowline EchoPod UG01 and UG03 series quick start provides basic mounting, setup, and use instructions for the ultrasonic liquid level switch, controller, and transmitter. It lists components such as a 4 ft (1.2 m) cable, Viton gasket, and optional USB key fob, and describes configuration through WebCal software before mounting.

The guide covers tank measurement, dimensional entry, tank level confirmation, writing configuration to the unit, mounting options and guidelines, stand-pipe installation, and wiring. It includes relay and power wiring notes, safety guidance, and common wiring examples for displays, controllers, and PLCs.

What's inside

  • Components
  • Configuring EchoPod
  • Mounting EchoPod
  • Important Mounting Guidelines
  • Mounting in Stand-Pipe
  • Wiring EchoPod
  • Common Wiring to Display, Controllers & PLCs

Specifications

Cable length4 ft (1.2 m)
Viton gasket2 in, P/N 210138 (G version only)
USB key fobP/N LI99-2001 (included with some models)
Maximum computer-to-sensor distance during configuration15 ft
Red and black wire extensionUp to 1,000 ft with 22-gauge or larger wire
Green and white wire extensionDo not extend beyond 15 ft
Supply voltageNever exceed 28 VDC
Relay powerDo not exceed 28 VDC
Mounting distance from side wallAt least 2 in
2 in diameter riser heightNo taller than 4 in
Larger diameter riser heightNo taller than 12 in
Riser height-to-diameter ratio2:1
Stand-pipe minimum diameter2 in
Stand-pipe bottom cut45 degrees
Pressure equalization hole1/4 in
Relay typeLatching relays

Frequently asked questions

What software is used to configure the EchoPod?

EchoPod is configured through WebCal, a PC software program.

What components are included with the sensor?

Depending on part number and configuration, EchoPod comes with a 4 ft cable, Viton gasket, Quick Start, and some models include a USB key fob.

What is the maximum distance between the computer and EchoPod during configuration?

The maximum distance is 15 feet.

What is the maximum supply voltage for EchoPod?

Supply voltage should never exceed 28 VDC.