The STC-106 is a miniature telecontrol device designed for monitoring computer rooms and other places with a large number of thermal resistors for data acquisition and control.
This manual describes the STC-106, a micro remote terminal unit (RTU) developed by Beijing Yikong Weiwang Technology Co., Ltd. for data acquisition and control in equipment-room monitoring and other applications with many RTD sensors. The unit provides 8 isolated PT100 RTD inputs and uses the company's bridge-circuit measurement technology with AC excitation, which the manual states eliminates temperature drift and lead-resistance effects and offers strong interference immunity.
The document covers the product design and system parameters, the RTD measurement principle, the MODBUS RTU communication protocol including supported function codes (03, 04, 06) and serial baud-rate configuration, installation and terminal definitions, typical applications built over GPRS or RS485, three-wire and two-wire RTD wiring, and ordering information. This manual is written in Chinese.
| RTD inputs | 8 isolated RTD inputs, 3-wire or 2-wire connection |
|---|---|
| Measurement range | -200℃ to 650℃ |
| Resolution | 0.1℃ |
| Accuracy | ±0.5% ±1.0℃ |
| Isolation voltage | Not less than 1500V (inputs and communication ports) |
| Communication interfaces | 2 isolated ports, RS232 or RS485, up to 115200 bps, MODBUS RTU |
| Power supply | DC 9-36V ±10% or AC 110-265V, consumption ≤1W |
| Operating temperature | -20℃ to 70℃ |
| Dimensions | 145 × 90 × 40 mm, approx. 0.3 kg |
| Mounting | DIN rail or bottom screw fixing, 5.08mm terminal pitch |
The factory default is 8 data bits, no parity, at 9600 bps.
It supports function code 03 (read holding registers), 04 (read input registers) and 06 (set single holding register).
No, addresses 00 and FF are broadcast addresses and must not be used, otherwise a system fault may occur.
It uses a three-wire RTD connection, which cancels the effect of lead resistance; a two-wire connection requires manual correction.