万能转换开关LW39-63 EN60947-5-1,GB 14048.5 is suitable for various control circuits, conversion of electrical measuring instruments, and remote control of distribution equipment. It can also be used to control the start, brake,正反转换向and speed control of small-capacity motors.
This is the Chinese-language user manual (使用说明书) for the LW39-63 series universal changeover switch (万能转换开关) from Suzhou Siemens Electric Co., Ltd. Tiantai Branch (APT brand). It states that the switch is used for switching in control circuits and electrical measuring instruments, remote control of distribution equipment, and for starting, braking, forward/reverse switching and speed control of small-capacity and two-speed motors.
The manual explains the model designation code, lists safety precautions (e.g. disconnect power before installation and wiring), gives technical parameters such as rated insulation voltage 690 V and thermal current 25 A, operating environment requirements, lamp box wiring schematics, and installation and mounting cutout dimensions for the LW39-63, LW39-63P, LW39-63DM, LW39-63YS and LW39-63/16 variants. This manual is written in Chinese.
| Rated insulation voltage (Ui) | 690 V |
|---|---|
| Conventional thermal current (Ith) | 25 A |
| Power-frequency withstand voltage | 1890 V / 5 s |
| Mechanical life | 300,000 operations |
| Electrical life | AC 200,000 / DC 100,000 operations |
| Fuse for rated limited short-circuit current test | NT00-40A |
| Max wire cross-section / wires per terminal | 10 mm², 2 wires |
| Min wire cross-section / wires per terminal | 2.5 mm², 2 wires |
| Terminal screw tightening torque | 2.5 N·m |
| Ambient temperature | -25°C to +55°C |
| Relative humidity | not exceeding 90% |
| Altitude | not exceeding 2000 m |
| Rated operating current, AC-15 | 22 A at 24 V, 16 A at 110 V, 8 A at 220 V, 6 A at 380 V |
| Rated operating current, AC-4 | 12 A |
| Rated operating current, AC-22A | 63 A |
It is used for switching in control circuits and electrical measuring instruments, remote control of distribution equipment, and starting, braking, reversing and speed control of small-capacity and two-speed motors.
The power supply must be cut off before installing and wiring the product, and wiring should follow the diagram and be checked before energizing.
Wire cross-sections from 2.5 mm² to 10 mm² can be connected, with up to 2 wires per terminal, tightened to 2.5 N·m.
It operates at -25°C to +55°C, relative humidity up to 90%, at altitudes up to 2000 m, installation category III, pollution degree 3.