The HT-B101 transformer neutral point discharge gap is a protection device suitable for power, metallurgy, chemical, coal and other industries.
This manual describes the HT-B101 series transformer neutral point grounding protection device manufactured by Nanjing Houtai Electric Technology Co., Ltd. The device is intended for transformer neutral points in 110 kV and higher voltage systems and consists of a high-voltage single-phase disconnector, a neutral point metal-oxide arrester, a current transformer and a discharge gap, allowing the neutral point to operate either grounded or ungrounded and protecting transformer insulation from voltage rises caused by lightning and faults.
The manual covers the product model designation, service environment, relevant national regulations, technical data for the GW13 and GW8 disconnector versions, outline and installation dimensions, transport and storage, installation requirements, and acceptance tests including arrester reference voltage, leakage current, disconnector operation and power-frequency discharge voltage tests. This manual is written in Chinese.
| Rated voltage (HT-B101-110) | 110 kV |
|---|---|
| Rated voltage (HT-B101-220) | 220 kV |
| Disconnector rated current (GW13 series) | 630 A |
| Disconnector rated current (GW8 series) | 400 A |
| Ambient temperature | -40 °C to +55 °C |
| Altitude | Not higher than 2000 m |
| Maximum wind speed | 35 m/s |
| Pollution level | Class III (2.8 kV/cm) |
| Ice thickness | 10 mm |
| Recommended arrester for 220 kV winding neutral point | Y1.5W-144/320 with 300 mm gap |
| Recommended arrester for 110 kV winding neutral point | Y1.5W-60/144 with 140 mm gap |
| Current transformer ratios | 10 kV, 100/5 to 600/5 |
| Rod gap material | φ16 mm galvanized round steel |
It is a neutral point grounding protection device for transformers of 110 kV voltage class and above, combining a disconnector, arrester, current transformer and discharge gap so the neutral point can run grounded or ungrounded.
It is for outdoor, pole-mounted combined installation at altitudes up to 2000 m, with ambient temperatures from -40 °C to +55 °C, maximum wind speed 35 m/s and ice thickness up to 10 mm.
Perform the power-frequency and DC 1 mA reference voltage tests and a leakage current test at 0.75 times the DC 1 mA reference voltage, where the leakage current must not exceed 50 μA; power-frequency discharge voltage tests on the arrester are strictly forbidden.
The disconnector must complete 10 no-load open and close operations, each reaching the fully open and fully closed positions without damage to any part.