Houtai HT-B101 Transformer Neutral Point Discharge Gap Instruction Manual

The HT-B101 transformer neutral point discharge gap is a protection device suitable for power, metallurgy, chemical, coal and other industries.


Houtai HT-B101 Transformer Neutral Point Discharge Gap Instruction Manual - cover page
Brand
Houtai
Category
Other products
Document type
User Manual
Language
Chinese
Pages
13
File format
PDF
File size
371 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
BD75DF7E9FBB1D56FB0BBBB6E9A49422

About this manual

This manual describes the HT-B101 series transformer neutral point grounding protection device manufactured by Nanjing Houtai Electric Technology Co., Ltd. The device is intended for transformer neutral points in 110 kV and higher voltage systems and consists of a high-voltage single-phase disconnector, a neutral point metal-oxide arrester, a current transformer and a discharge gap, allowing the neutral point to operate either grounded or ungrounded and protecting transformer insulation from voltage rises caused by lightning and faults.

The manual covers the product model designation, service environment, relevant national regulations, technical data for the GW13 and GW8 disconnector versions, outline and installation dimensions, transport and storage, installation requirements, and acceptance tests including arrester reference voltage, leakage current, disconnector operation and power-frequency discharge voltage tests. This manual is written in Chinese.

What's inside

  • 概述 (Overview)
  • 引用标准 (Referenced standards)
  • 产品型号说明 (Product model designation)
  • 使用环境 (Service environment)
  • 国家相关规定 (National regulations)
  • 产品特点 (Product features)
  • 外形及安装尺寸 (Outline and installation dimensions)
  • 运输及储存 (Transport and storage)
  • 安装要求 (Installation requirements)
  • 产品验收 (Product acceptance)

Specifications

Rated voltage (HT-B101-110)110 kV
Rated voltage (HT-B101-220)220 kV
Disconnector rated current (GW13 series)630 A
Disconnector rated current (GW8 series)400 A
Ambient temperature-40 °C to +55 °C
AltitudeNot higher than 2000 m
Maximum wind speed35 m/s
Pollution levelClass III (2.8 kV/cm)
Ice thickness10 mm
Recommended arrester for 220 kV winding neutral pointY1.5W-144/320 with 300 mm gap
Recommended arrester for 110 kV winding neutral pointY1.5W-60/144 with 140 mm gap
Current transformer ratios10 kV, 100/5 to 600/5
Rod gap materialφ16 mm galvanized round steel

Frequently asked questions

What is the HT-B101 device used for?

It is a neutral point grounding protection device for transformers of 110 kV voltage class and above, combining a disconnector, arrester, current transformer and discharge gap so the neutral point can run grounded or ungrounded.

What environment can the device be installed in?

It is for outdoor, pole-mounted combined installation at altitudes up to 2000 m, with ambient temperatures from -40 °C to +55 °C, maximum wind speed 35 m/s and ice thickness up to 10 mm.

How is the zinc-oxide arrester tested during acceptance?

Perform the power-frequency and DC 1 mA reference voltage tests and a leakage current test at 0.75 times the DC 1 mA reference voltage, where the leakage current must not exceed 50 μA; power-frequency discharge voltage tests on the arrester are strictly forbidden.

How many no-load operations must the disconnector pass during acceptance?

The disconnector must complete 10 no-load open and close operations, each reaching the fully open and fully closed positions without damage to any part.