Houtai HT-B101 Transformer Neutral Point Discharge Gap Instruction Manual
This manual describes the HT-B101 series transformer neutral point grounding protection device manufactured by Nanjing Houtai Electric Technology Co., Ltd. The device is intended for transformer neutral points in 110 kV and higher voltage systems and consists of a high-voltage single-phase disconnector, a neutral point metal-oxide arrester, a current transformer and a discharge gap, allowing the neutral point to operate either grounded or ungrounded and protecting transformer insulation from voltage rises caused by lightning and faults.
The manual covers the product model designation, service environment, relevant national regulations, technical data for the GW13 and GW8 disconnector versions, outline and installation dimensions, transport and storage, installation requirements, and acceptance tests including arrester reference voltage, leakage current, disconnector operation and power-frequency discharge voltage tests. This manual is written in Chinese.
Covers: 概述 (Overview) · 引用标准 (Referenced standards) · 产品型号说明 (Product model designation) · 使用环境 (Service environment) · 国家相关规定 (National regulations) · 产品特点 (Product features)
Latest Houtai manuals
Houtai HT-B101 Transformer Neutral Point Discharge Gap Instruction Manual
User Manual 13 pages · 371 KB · ZHChinese instruction manual for the Houtai HT-B101 transformer neutral point discharge gap protection device for 110 kV and 220 kV transformers, with specs…
Which document do I need?
User Manual
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in Houtai manuals
What is the HT-B101 device used for?
It is a neutral point grounding protection device for transformers of 110 kV voltage class and above, combining a disconnector, arrester, current transformer and discharge gap so the neutral point can run grounded or ungrounded.
From: Houtai HT-B101 Transformer Neutral Point Discharge Gap Instruction Manual
What environment can the device be installed in?
It is for outdoor, pole-mounted combined installation at altitudes up to 2000 m, with ambient temperatures from -40 °C to +55 °C, maximum wind speed 35 m/s and ice thickness up to 10 mm.