IPAC-5941D series transformer protection device is suitable for 220kV and below voltage level digital substation, need to provide double sets of main protection, double sets of backup protection of various wiring methods of transformer.
The iPACS-5941D is a transformer protection device for 220 kV and below digital substations requiring dual main protection and dual back-up protection for transformers with various wiring. The standardized version is for 220 kV and below three-winding transformers, with a maximum configuration of five-side differential protection and four-side back-up protection, and it supports IEC61850-9-1, IEC61850-9-2, IEC60044 sampling and GOOSE switch quantities.
The manual documents mechanical and environmental limits, rated electrical parameters, protection functions such as differential, back-up overcurrent, zero-sequence and alarm functions, setting lists and user selections, hardware layout and wiring, and appendices on communication protocols. This manual is written in Chinese.
| Enclosure dimensions | 261 mm x 265.9 mm x 177 mm (4U) |
|---|---|
| Normal operating temperature | 0 to 40 C |
| Limit operating temperature | -10 to 50 C |
| Storage and transport temperature | -25 to 70 C |
| Frequency | 50 Hz |
| DC power supply | 220 V or 110 V, tolerance +15% / -20% |
| AC voltage | 57.7 V and 100 V |
| AC current | 1 A and 5 A |
| DC power consumption | Normal <=20 W; tripping <=30 W |
| Differential quick trip time | <=30 ms (at 1.5 times setting) |
| Proportional differential trip time | <=40 ms (at 2 times setting) |
| Differential quick trip setting | 2 Ie to 20 Ie |
| Proportional braking coefficient | 0.2 to 0.75 |
| Second harmonic braking coefficient | 0.05 to 0.30 |
| TA alarm differential setting | 0.1 Ie to 1 Ie |
| Back-up current setting | 0.5 A to 100 A (In=5 A); 0.1 A to 20 A (In=1 A) |
| Back-up voltage setting | 2 V to 100 V |
| Gap zero-sequence overvoltage setting | 10 V to 220 V; 0.1 A to 30 A (In=1 A) |
| Back-up zero-sequence voltage setting | 2 V to 150 V |
| Current setting error | Not more than +/-5% |
| Voltage setting error | Not more than +/-5% |
| Time setting error | <=3% of setting + 40 ms |
| Harmonic braking coefficient error | Not more than +/-5% |
| Braking coefficient error | Not more than +/-5% |
| Direction element boundary error | Not more than +/-3 deg |
| Signal contact capacity | Long-term 8 A; breaking 0.3 A (DC 220 V, V/R 1 ms) |
| Other auxiliary relay contact capacity | Long-term 5 A; breaking 0.2 A (DC 220 V, V/R 1 ms) |
| Back-panel communication interfaces | Four 10/100 M Ethernet interfaces, one synchronous clock interface, one printer interface |
| Standard configuration 1 | 10 LC fiber Ethernet interfaces |
It is a transformer protection device for 220 kV and below digital substations requiring dual main protection and dual back-up protection for transformers with various wiring.
It supports IEC61850-9-1, IEC61850-9-2, or IEC60044 sampling data reception, and GOOSE is supported for switch quantities.
No. It is for design selection reference only and may differ slightly from the actual product; design drawings should be requested from the company.
The enclosure dimensions are 261 mm x 265.9 mm x 177 mm (4U).