The device is suitable for voltage levels of 220kV and below, and provides various wiring methods for transformers that require dual main protection and dual backup protection.
The PACS-5941T2-G series transformer protection device applies to 220 kV and below voltage levels and is intended for transformers requiring dual main protection and dual backup protection. The model described is a conventional-station protection device with conventional analog sampling and binary output, configured according to Q/GDW 175-2013.
The manual contains an overview, protection configuration, technical parameters, protection working principles, setting value lists and user selection, hardware description, and operation and running instructions. This manual is written in Chinese.
| Applicable voltage level | 220 kV and below |
|---|---|
| Sampling and output | Conventional analog sampling, binary output |
| Overload protection setting | 1.1 times rated current, 10 s delay, alarm |
| Zero-sequence voltage setting | 180 V external, 120 V self-produced |
It applies to 220 kV and below voltage levels, for transformers requiring dual main and dual backup protection.
The device is configured according to Q/GDW 175-2013, the standardized design specification for transformer, high-voltage shunt reactor and busbar protection and auxiliary devices.
It uses conventional analog sampling and binary output.
The setting is fixed at 1.1 times the rated current of that side, with a 10 s delay, and it operates an alarm.