YDQ series inflatable test transformer adopts high-quality cold-rolled DQ-151 oriented silicon steel sheet to stack into a multi-stage cylindrical frame iron core, and the outer casing is cylindrical and filled with sf6 gas.
This manual describes the YDQ series gas-filled (充气式) test transformer, a test device for power equipment detection and preventive testing. Unlike traditional oil-immersed test transformers, it uses sulfur hexafluoride (SF6) gas as the insulating medium, weighs 20%–60% less depending on voltage and capacity class, and a single unit can reach voltage levels up to 300 kV. The YDQ(JZ) version provides AC power-frequency high-voltage output, while the YDQ(J) version includes a high-voltage rectifier stack so a short-circuit rod can be inserted or removed to switch between AC and DC high-voltage output.
The manual covers the product structure, model designation, working principle, control circuit diagram, test site wiring (AC withstand voltage, DC leakage, and cascade/series combination tests with the YDQ(C) units), step-by-step operating procedure, safety precautions, maintenance and gas refilling, service conditions, and rated parameter tables. A second section explains the matching control box/console (XC and TC series), including its panel layout, operating procedure, service conditions and packing list. This manual is written in Chinese.
| Maximum single-unit voltage | 300 kV |
|---|---|
| Weight reduction vs. oil-immersed type | 20%–60% |
| Factory gas pressure | 0.3–0.4 MPa |
| Maximum refilling pressure | 0.55 MPa |
| Normal gas leakage rate | approx. 0.05 MPa per 4 years |
| Ambient temperature (operating) | 0~40℃ |
| Altitude (operating) | <2000 m |
| Relative humidity (operating) | <85% |
| Rated capacity range (YDQ(JZ) table) | 1.5–50 kVA (50/100/150/200 kV high-voltage side) |
It uses sulfur hexafluoride (SF6) gas as the insulating medium instead of oil, chosen for its insulation, arc-quenching and non-flammable properties.
On the YDQ(J) model, insert the short-circuit rod into hole J for AC withstand voltage tests and remove it for DC leakage tests.
Check that the pressure gauge shows the internal gas pressure is normal, at least 0.3 MPa.
Refill when the pressure drops to 0.3 MPa, using the manufacturer's dedicated gas-filling nozzle and a small SF6 cylinder; never exceed 0.55 MPa.