The main features of the motor protection circuit breaker are: 50% less wiring, compact structure, 57% less installation space, environmentally friendly design and high safety.
This catalog from Shihlin Electric (SEEC) covers its MMS series manual motor starters (電動機保護斷路器), models MR-32S, MR-32R and MR-65R. The starters are for circuits up to 690 V AC at 50/60 Hz with rated operating currents of 0.1–65 A, providing overload, phase-loss and short-circuit protection for three-phase motors, infrequent starting/stopping, and isolator function. According to the catalog, replacing a molded-case breaker plus thermal overload relay with one MMS reduces wiring work by 50% and installation space by 57%, and the units meet IEC 60947-2, IEC 60947-4-1, UL 508 and TUV.
The document lists main technical parameters and model designation, rated capacity tables (Icu/Ics at 230/240 V through 690 V), optional accessories (auxiliary contact blocks, shunt trip, undervoltage trip, short-circuit and fault signal contact blocks), application wiring examples with Shihlin contactors and wiring modules (WKM/WKX series), tripping characteristic curves, and outline/installation dimensions and weights. This manual is written in Chinese.
| Poles | 3P |
|---|---|
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Rated frequency | 50/60 Hz |
| Rated operating current range | 0.1–65 A |
| Protection class | IP20 |
| Mechanical life (MR-32) | 100,000 operations |
| Electrical life (MR-32) | 100,000 operations |
| Mechanical/electrical life (MR-65R) | 50,000 operations |
| Operating temperature | -25 to 55 °C |
| Storage temperature | -50 to 80 °C |
| Temperature compensation | Automatic |
| Phase-loss protection | Provided |
| Weight MR-32S / MR-32R / MR-65R | 0.26 kg / 0.3 kg / 1 kg |
They comply with IEC 60947-2, IEC 60947-4-1, UL 508 and TUV.
Adjust it only within the rated operating current range and do not rotate it more than 360 degrees, otherwise the function may fail.