This product is an infrared point extended gas detector with the following features: 1. Wide detection range, can detect a variety of gases; 2. Fast response speed, can detect gas leaks in a short time; 3. High precision, can accurately detect gas concentration; 4. High reliability, can work in harsh environments.
This operating manual (document 850-814800-R04) describes the Simtronics GD10PE infrared point extended gas detector, which uses a dual wavelength, dual path IR-absorption measurement with a silicon-based solid-state infrared source. It is designed for fast detection of low hydrocarbon gas concentrations in critical applications such as HVAC air intakes, gas turbine packages and pump rooms, and can be duct mounted or used as a standalone point detector with weather protection.
The manual covers product description, technical specifications, installation (positioning, fixing, weather protection, duct or pipe mounting, electrical connection), commissioning, operation via the 4–20 mA output and HART interface, maintenance including lens cleaning, function and calibration tests, re-zeroing and fault finding, plus warnings, warranty, certifications, accessories and spare parts.
| Detection method | IR-absorption, dual wavelength, dual path |
|---|---|
| Detection range | 0-20% LEL (0-1% Vol.) methane |
| Gases detected | Hydrocarbons |
| IR source | Solid state IR source, 50 Hz flash |
| Accuracy | ±1%LEL (0-10% LEL reading), ±1.4%LEL (10-20% LEL reading) |
| Response time | 0.6 sec. at 4% LEL test gas (20%LEL reading: 1 sec.) |
| Start-up time | Less than 60 sec. |
| Output signal | 4–20 mA current source, max. load impedance 500 Ohm; HART interface |
| Power supply | 24 V DC, range 18-32 V DC |
| Power consumption | Approx. 3.5 W |
| Operating temperature | -40°C to +65°C; probe inside duct up to +85°C |
| Housing | Stainless steel SIS2343 (ASTM 316), Exd IIC T6 Gb, IP66/IP67 |
| Weight | Approx. 6.5 kg |
| Dimensions | 805L x 104W x 106H (mm) |
| Warranty | 5 years full warranty on complete instrument; 15 years on IR sources |
No. The GD10PE stays within its specifications for its service lifetime without recalibration; calibration is factory set.
Inside an enclosed area it should be mounted high in the area to be protected or immediately above potential leakage sites, since methane is lighter than air.
Always use weather protection if the detector is mounted standalone or exposed to weather, water or rain, but do not mount it where it could be exposed to water drenching.
It should be mounted so that the longitudinal axis of the detector is horizontal, which prevents accumulation of water and dust on the optics.