Operating Manual of Infrared Point Gas Detector GD10-P00
The GD10P is an infrared point gas detector intended for gas hazard detection in industrial environments, from boiler plant rooms to offshore petrochemical installations. The manual describes its silicon-based solid-state infrared source, dual-wavelength dual-path IR absorption design, continuous self-test, and suitability for inert gas atmospheres without oxygen.
The document covers installation and positioning, weather protection and duct mounting, electrical connection, commissioning, operation with the analog output and HART interface, maintenance, warnings, warranty, certifications, and spare parts. Listed specifications include a 0–100% LEL methane version with 5-second response time, 24 V DC power, 4–20 mA output, stainless steel housing, and a 5-year instrument warranty with 15-year IR-source warranty.
| Detection method | IR-absorption, dual wavelength, dual path |
|---|---|
| Gases detected | Detector versions for several hydrocarbons as well as CO2 |
| Response time T90 | 6 sec (optional 1.6 sec) |
| Power supply | 24 V DC, range 18–32 V DC |
| Power consumption | Approx. 3.5 W |
| Output signal | Current source 4–20 mA, max. load impedance 500 Ohm |
| Operating temperature | -40°C to +65°C (-40°F to +149°F) |
| Housing material | Stainless steel SIS2343 (ASTM 316) |
| Weight | Approx. 2.9 kg (6.4 Lbs) |
No. The manual states that oxygen is not required for correct measurement, making the detector suitable for inert gas atmospheres.
It provides a 4–20 mA current source output with a maximum load impedance of 500 Ohm; a current sink option and HART interface are also listed.
It is mounted with a projecting mounting leg using two M8 screws and washers, or with the Duct Mounting Flange Kit using four M8 screws.
About 3 minutes; the analog output drops to 1 mA during the process and returns to 4 mA when zeroing is complete.