Simtronics GD10-P00 Infrared Point Gas Detector Operating Manual

Operating Manual of Infrared Point Gas Detector GD10-P00


Simtronics GD10-P00 Infrared Point Gas Detector Operating Manual - cover page
Brand
Simtronics
Category
detectors
Document type
User Manual
Language
English
Pages
32
File format
PDF
File size
855 KB
Published
15 October, 2023
Updated
15 October, 2023
MD5 checksum
1E0DB27B651B7125AFC603E3380BBE52

About this manual

The GD10P is an infrared point gas detector intended for gas hazard detection in industrial environments, from boiler plant rooms to offshore petrochemical installations. The manual describes its silicon-based solid-state infrared source, dual-wavelength dual-path IR absorption design, continuous self-test, and suitability for inert gas atmospheres without oxygen.

The document covers installation and positioning, weather protection and duct mounting, electrical connection, commissioning, operation with the analog output and HART interface, maintenance, warnings, warranty, certifications, and spare parts. Listed specifications include a 0–100% LEL methane version with 5-second response time, 24 V DC power, 4–20 mA output, stainless steel housing, and a 5-year instrument warranty with 15-year IR-source warranty.

What's inside

  • Product description
  • Technical specifications
  • Installation
  • Commissioning
  • Operation
  • Maintenance
  • Warnings
  • Warranty
  • Certifications and standards
  • Accessories and spare parts

Specifications

Detection methodIR-absorption, dual wavelength, dual path
Gases detectedDetector versions for several hydrocarbons as well as CO2
Response time T906 sec (optional 1.6 sec)
Power supply24 V DC, range 18–32 V DC
Power consumptionApprox. 3.5 W
Output signalCurrent source 4–20 mA, max. load impedance 500 Ohm
Operating temperature-40°C to +65°C (-40°F to +149°F)
Housing materialStainless steel SIS2343 (ASTM 316)
WeightApprox. 2.9 kg (6.4 Lbs)

Frequently asked questions

Does the GD10-P00 need oxygen to work?

No. The manual states that oxygen is not required for correct measurement, making the detector suitable for inert gas atmospheres.

What is the standard output signal?

It provides a 4–20 mA current source output with a maximum load impedance of 500 Ohm; a current sink option and HART interface are also listed.

How is the detector mounted?

It is mounted with a projecting mounting leg using two M8 screws and washers, or with the Duct Mounting Flange Kit using four M8 screws.

How long does HART zeroing take?

About 3 minutes; the analog output drops to 1 mA during the process and returns to 4 mA when zeroing is complete.