This document describes the installation instructions for Haier air conditioners.
This installation manual is for Electrolux CI36F/CE36F, CI48F/CE48F and CI60F/CE60F floor/ceiling air conditioners. It is intended for trained installers and covers safety, product description, indoor and outdoor unit installation, connection piping, system vacuum, additional gas charge, drainage, electrical installation, operation testing and technical specifications.
The manual also lists installation location requirements, accessories, refrigerant connection pipe diameters, maximum height and distance limits between units, and electrical connection notes. This manual is written in Portuguese.
| Liquid line connection pipe diameter | 9.52 mm (3/8 in) x 0.8 mm |
|---|---|
| Suction line connection pipe diameter | 19.0 mm (3/4 in) x 1.2 mm |
| Maximum height difference between units | Less than 15 m |
| Maximum distance between units along piping | Less than 30 m |
| Suspension screw tightening force | 980 to 1470 N |
Installation must be performed by trained, qualified professionals; contact the authorized Electrolux service network.
The distance along the connecting piping must be less than 30 meters.
The height difference must be less than 15 meters.