The Universal Interface Card (UIC) provides signal scaling and an isolation interface to pulse flowmeter outputs, and re-transmits to PLC/computer inputs. Three model variants are available.
This ManuFlo datasheet covers the UIC Universal Pulse Interface Card, a 24V DC powered card that scales and isolates pulse flowmeter outputs and re-transmits them to PLC or computer inputs. It is suitable with most NPN and contact closure flowmeters and is fully isolated to the PLC input. Three model variants are listed: UIC/A2-24DC with 24–250 vac switching, UIC/A1-24DC with 110–240 vac switching, and UIC/D-24DC with 5–30 VDC NPN/PNP switching.
The document describes calibration with three decade rotary switches marked H, T and U, gives wiring and connection details, commissioning steps and a troubleshooting guide, and includes calibration value tables for MES 20/25/32/40 mm flowmeters, RPFS-P paddlewheel meters and MAGFLOWS meters such as KMS, MFS and RMS. Specifications for supply voltage, input, pulse frequency and the switching variants are listed.
| Supply voltage | +24V DC |
|---|---|
| Voltage to flowmeter | +12 VDC regulated, supplied by the UIC to power the flowmeter |
| Input | NPN transistor or contact closure input |
| Pulse input frequency max | 2 kHz for the standard x10 input (e.g. with MES20) |
| UIC/A2-24DC AC switching | 24 - 250 vac switching up to 1 Amp via CRYDOM AO241 solid state opto triac, surge protection to 2500 V RMS |
| UIC/A1-24DC AC switching | 110-240 vac switching via Motorola 3041 opto |
| UIC/D-24DC open collector switching | 5-30 VDC via 4N33 Motorola opto, open collector (sink or source), surge protection to 7500 V RMS |
| Current draw | Each UIC card/flowmeter can draw up to 25mA |
The card is powered from a +24V DC supply only, and it in turn supplies regulated +12 VDC to the flowmeter where required.
Pulse output rate to AC inputs must not exceed 13Hz, because faster pulse rates will cause the computer to miss pulses and overdose.
Use a small flat-bladed screwdriver in the three decade rotary switches numbered 0-9 and marked H (Hundreds), T (Tens) and U (Units), turning the arrow to the desired number.
Check that the HTU setting is not H=0 T=0 U=0 and is correct for the application; set a value such as HTU=100 with the power off, then power up again and check the output LED.