GCI single-phase fifth-generation string grid-connected inverter can convert the DC power generated by the photovoltaic panels into AC power and connect it to the grid.
This Chinese user manual covers the Ginlong GCI-1P7K-5G and GCI-1P8K-5G single-phase fifth-generation string grid-connected photovoltaic inverters. It explains safety instructions, the operation interface, product installation, electrical connection, startup and shutdown, general operation, maintenance, and troubleshooting.
The manual lists the inverter, mounting plate, DC connectors, optional WiFi/GPRS monitoring stick, AC connector, screws and documents in the packing list. It also gives installation clearance requirements, external grounding details, and DC cable preparation steps. This manual is written in Chinese.
| Models | GCI-1P7K-5G and GCI-1P8K-5G |
|---|---|
| Operating ambient temperature | -25 to 60 °C |
| Surface temperature | Up to 75 °C |
| Minimum clearance between inverters | 300 mm |
| Minimum height above ground | More than 500 mm |
| Recommended DC cable cross-section | 4.0 mm² (12 AWG); range 4.0–6.0 mm² |
| DC cable strip length | 7 ± 0.5 mm |
| External ground screw torque | 2 Nm |
The manual covers the Ginlong GCI-1P7K-5G and GCI-1P8K-5G models.
The inverter is designed to operate in an ambient temperature range of -25 to 60 °C.
The recommended DC cable size is 4.0 mm² (12 AWG), within a 4.0–6.0 mm² range.
Wait 5 minutes after shutting off all power supplies before removing the top cover.