The MD9207 is a temperature difference automatic controller that can measure three temperature points, namely temperature 0, temperature 1, and temperature 2. A single-pole double-throw relay 0 is used for control corresponding to temperature 0, and a single-pole double-throw relay 1 (relay type) and an analog output are used for control corresponding to the temperature difference Δ between temperature 1 and temperature 2. The MD9207 can also execute different controls according to the time period, and a total of ten time periods can be set. It is also possible to set whether relay 0 is controlled by the temperature difference Δ.
This manual describes the MD9207 temperature difference automatic controller from Beijing Micronode Technology Co., Ltd. (Nicronode). The instrument is a microcontroller-based measuring and control device that uses temperature and temperature difference to drive relay outputs and an analog output, and can be programmed with ten time periods, each running a different type of control. It measures three temperature points (temperature 0, 1 and 2); temperature 0 controls relay 0, while the difference between temperature 1 and temperature 2 controls relay 1 and an analog output. Models with the C suffix add RS485 communication for data transfer to a host computer.
The manual covers model naming, hardware specifications, panel layout and rear-panel wiring diagrams for both the relay-output and OC-gate-output versions, the three operating states (setting, working and non-working), basic and secondary parameter setting, restoring factory defaults, descriptions of the heating and temperature-difference control processes, and an explanation of hysteresis (回差) control. This manual is written in Chinese.
| Temperature measurement range | 0°C to +99.9°C (sensor cable up to 100 m) |
|---|---|
| Temperature resolution | 0.0625°C |
| Temperature accuracy | ±0.5 |
| Temperature inputs | 3 channels, one sensor per channel |
| Display | LED digital display, 6 keys |
| Isolation voltage | 1500 V |
| Line protection | 600 W transient overvoltage (TVS), overcurrent (PTC), ESD protection |
| Watchdog | Hardware watchdog, 1.5 s overflow time |
| Power supply | 85–265 VAC, ≤5 W |
| Operating temperature | -25°C to +85°C |
| Dimensions | 160 × 120 × 80 mm |
| Analog output | 0–10 V (DC) |
| OC gate output | 2 OC gate outputs, can drive SSR 3–4.5 VDC, 100 mA |
| Time periods | 10 programmable time periods (A, B, C, D, E, F, H, L, N, P) |
In the working state, press the Stop key for 4 to 6 seconds until the accumulated working time window shows 000.0, then release; the current work stops and all control outputs are turned off.
Each time period defaults to a temperature 0 setting of 38°C, a time of 12 hours and a temperature difference of 1.5°C; secondary parameters default to HE1 0.5, HE2 0.5, HE3 1.0 and EE/0E1/0E2/0E3 all 0.
Hold the Display key before powering on, then power up while keeping it pressed; after 3–4 seconds the communication parameters reset to address 01 and baud rate code 06 (9600 BPS).
It can measure three temperature points (temperature 0, 1 and 2), each on its own sensor channel, and the Δ temperature window shows temperature 1 minus temperature 2.