The MS-100G Handheld Special Transformer Turns Ratio Tester is a high-precision, high-reliability transformer turns ratio tester. It adopts a three-phase precision inverter power supply, rather than a single-phase AC power supply as the measurement voltage, eliminating the influence of harmonic components of the AC power supply during measurement and making the measurement more accurate.
This is the Chinese user manual for the MSDQ MS-100G handheld special transformer turns ratio (voltage ratio) tester. It is used to test the turns ratio or voltage ratio of power transformers during production, before commissioning, and in preventive maintenance, to check ratio correctness, tap changer condition, inter-turn short circuits, and whether transformers can operate in parallel.
The manual describes the instrument's features, including a built-in three-phase precision inverter power source, automatic identification of transformer connection groups 0-11, protection functions, a 7-inch color touch screen, external printer support, and control via an Android phone APP. It covers menu operation, three-phase/single-phase/Z-type/Scott connection measurements, data storage and query, system settings, wiring examples, precautions, self-check methods, and storage and warranty information. This manual is written in Chinese.
| Measurement range | 0.9~10000 |
|---|---|
| Measurement accuracy | ±0.1%+2 digits (0.9-500), ±0.2%+2 digits (501-2000), ±0.5%+2 digits (2001-10000) |
| Output voltage | Automatically adjusted according to load |
| Resolution | Minimum 0.0001 |
| Power supply | AC220V±10% 50±1Hz |
| Operating temperature | -10℃~40℃ |
| Relative humidity | ≤85%, non-condensing |
| Display | 7-inch HD color touch screen |
| Tap positions | Up to 99 tap positions |
Connect the test leads together, select Y-y-0 or D-d-0 as the connection type, and start a measurement. A reading of 1.0000 indicates the instrument is normal.
Tap "蓝牙" (Bluetooth) in the system settings to display a QR code, scan it with the dedicated APP downloaded on the phone, and the phone can then control the instrument throughout the test.
Ratio is the measured high-voltage to low-voltage voltage ratio when three-phase power is applied, while turns ratio is the ratio of winding turns. For a star-connected high voltage and delta-connected low voltage transformer, the ratio is √3 times the turns ratio.
After a test, tap 存储 to save data to the instrument and a USB drive, or tap 打印 to print the test data via the external printer interface.