This universal dimming actuator is suitable for switching and dimming incandescent lamps, high-voltage halogen lamps, dimmable high-voltage LED lamps, dimmable energy-saving lamps, dimmable inductive transformers (with low-voltage halogen lamps or low-voltage LED lamps), and dimmable electronic transformers (with low-voltage halogen lamps or low-voltage LED lamps).
This manual covers the REGHE universal dimming actuator modules in 1-gang, 2-gang and 4-gang versions, product numbers 3901, 3902 and 3904. The devices are KNX system products mounted on a support rail in a distribution box according to EN 60715, and the document describes their structure, functions, manual operation with the keys and status LEDs, and the information intended for electrical professionals.
The text lists the supported loads — incandescent lamps, high-voltage halogen lamps, dimmable high-voltage LED lamps and energy-saving lamps, and dimmable inductive or electronic transformers with low-voltage halogen or LED lamps — together with connection limits such as 600 W of high-voltage LED or energy-saving lamps per 16 A circuit breaker, 950 W for paralleled outputs on the 4-gang version, and speed control of single-phase motors on the 1-gang version only. Installation, connection examples, changing the connected load type and fitting the cover are also described. This manual is written in Chinese.
| Available versions | 1-gang (3901), 2-gang (3902), 4-gang (3904) |
|---|---|
| Mounting | Support rail in distribution box per EN 60715 |
| HV LED / energy-saving lamp load per 16 A circuit breaker | max. 600 W |
| Paralleled outputs (4-gang only) | luminaire load up to 950 W |
| Paralleled output capacity | max. 95 % each time |
| Inductive transformer operation | at least 85 % of rated load |
| Mixed load with inductive transformer | resistive load max. 50 % |
| Required safety isolating transformer | EN 61558-2-6 (VDE 0570, part 2-6) |
| Distance between devices | 18 mm (1 TE) |
| Behaviour after power failure | actuator switches off if the outage lasts more than about 5 s |
Press and hold key c for at least 5 seconds. LED c lights up and the status LEDs A1... flash.
No. Capacitive loads such as electronic transformers and inductive loads such as inductive transformers must not be connected together on one dimmer output.
Yes, but only on the 4-gang dimming actuator, where several dimming outputs can be combined for dimming a larger load up to 950 W.
The dimming principle is set to "conventional" in the delivery state.