REGHE 3901/3902/3904 Universal Dimming Actuator User Manual

This universal dimming actuator is suitable for switching and dimming incandescent lamps, high-voltage halogen lamps, dimmable high-voltage LED lamps, dimmable energy-saving lamps, dimmable inductive transformers (with low-voltage halogen lamps or low-voltage LED lamps), and dimmable electronic transformers (with low-voltage halogen lamps or low-voltage LED lamps).


REGHE 3901/3902/3904 Universal Dimming Actuator User Manual - cover page
Brand
REGHE
Category
lighting
Document type
User Manual
Language
Chinese
Pages
16
File format
PDF
File size
1.1 MB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
746CF25C850F5F094AD0F0C36B2AFB64

About this manual

This manual covers the REGHE universal dimming actuator modules in 1-gang, 2-gang and 4-gang versions, product numbers 3901, 3902 and 3904. The devices are KNX system products mounted on a support rail in a distribution box according to EN 60715, and the document describes their structure, functions, manual operation with the keys and status LEDs, and the information intended for electrical professionals.

The text lists the supported loads — incandescent lamps, high-voltage halogen lamps, dimmable high-voltage LED lamps and energy-saving lamps, and dimmable inductive or electronic transformers with low-voltage halogen or LED lamps — together with connection limits such as 600 W of high-voltage LED or energy-saving lamps per 16 A circuit breaker, 950 W for paralleled outputs on the 4-gang version, and speed control of single-phase motors on the 1-gang version only. Installation, connection examples, changing the connected load type and fitting the cover are also described. This manual is written in Chinese.

What's inside

  • Safety guidelines
  • Device structure
  • Functions and normal applications
  • Product characteristics
  • Operating elements and status display
  • Operating modes (bus, temporary manual, permanent manual)
  • Operating the outputs
  • Installation and electrical connection
  • Connecting luminaire loads
  • Changing the connected load type

Specifications

Available versions1-gang (3901), 2-gang (3902), 4-gang (3904)
MountingSupport rail in distribution box per EN 60715
HV LED / energy-saving lamp load per 16 A circuit breakermax. 600 W
Paralleled outputs (4-gang only)luminaire load up to 950 W
Paralleled output capacitymax. 95 % each time
Inductive transformer operationat least 85 % of rated load
Mixed load with inductive transformerresistive load max. 50 %
Required safety isolating transformerEN 61558-2-6 (VDE 0570, part 2-6)
Distance between devices18 mm (1 TE)
Behaviour after power failureactuator switches off if the outage lasts more than about 5 s

Frequently asked questions

How is permanent manual operation switched on?

Press and hold key c for at least 5 seconds. LED c lights up and the status LEDs A1... flash.

Can capacitive and inductive loads be connected to the same dimmer output?

No. Capacitive loads such as electronic transformers and inductive loads such as inductive transformers must not be connected together on one dimmer output.

Can several outputs be combined for a larger load?

Yes, but only on the 4-gang dimming actuator, where several dimming outputs can be combined for dimming a larger load up to 950 W.

Which dimming principle is set on delivery?

The dimming principle is set to "conventional" in the delivery state.

Download PDF (1.1 MB)