REGHE 3901/3902/3904 Universal Dimming Actuator User Manual
This manual covers the REGHE universal dimming actuator modules in 1-gang, 2-gang and 4-gang versions, product numbers 3901, 3902 and 3904. The devices are KNX system products mounted on a support rail in a distribution box according to EN 60715, and the document describes their structure, functions, manual operation with the keys and status LEDs, and the information intended for electrical professionals.
The text lists the supported loads — incandescent lamps, high-voltage halogen lamps, dimmable high-voltage LED lamps and energy-saving lamps, and dimmable inductive or electronic transformers with low-voltage halogen or LED lamps — together with connection limits such as 600 W of high-voltage LED or energy-saving lamps per 16 A circuit breaker, 950 W for paralleled outputs on the 4-gang version, and speed control of single-phase motors on the 1-gang version only. Installation, connection examples, changing the connected load type and fitting the cover are also described. This manual is written in Chinese.
Covers: Safety guidelines · Device structure · Functions and normal applications · Product characteristics · Operating elements and status display · Operating modes (bus, temporary manual, permanent manual)
Latest REGHE manuals
REGHE 3901/3902/3904 Universal Dimming Actuator User Manual
User Manual 16 pages · 1.1 MB · ZHUser manual for REGHE 3901, 3902 and 3904 KNX universal dimming actuators: safety notes, device layout, manual operation, installation and load connection.
Which document do I need?
User Manual
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in REGHE manuals
How is permanent manual operation switched on?
Press and hold key c for at least 5 seconds. LED c lights up and the status LEDs A1... flash.
From: REGHE 3901/3902/3904 Universal Dimming Actuator User Manual
Can capacitive and inductive loads be connected to the same dimmer output?
No. Capacitive loads such as electronic transformers and inductive loads such as inductive transformers must not be connected together on one dimmer output.