EDT-PD2 Double-Channel Digital Time Switch Operating Instruction

The EDT-PD2 digital time switch is used for realization of time functions in the control systems and automation. It operates according to the set time schedule planned by the user. There is an internal battery which can protect real time clock and all the settings when the electric power supply is off.


EDT-PD2 Double-Channel Digital Time Switch Operating Instruction - cover page
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
6
File format
PDF
File size
1.8 MB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
0F325CE5573E5AC8219A60596D256690

About this manual

EDT-PD2 is a double-channel digital weekly time switch with a backlighted LCD display and a 10-year power reserve. It is mounted on a TH-35 rail and operates from a 24-264 V AC/DC supply.

This operating instruction describes initial setup, time and date setting, weekly and daily programs, pulse output, holiday mode, summer/winter switching, language selection, manual control, reset, and the wiring diagram.

What's inside

  • Initial operation
  • Time setting
  • Date setting
  • Program setting
  • Pulse setting
  • Holiday program
  • Summer/winter switchover
  • Language setting
  • Reset
  • Wiring diagram

Specifications

Rated voltageAC/DC 24-264 V
Rated frequency50/60 Hz
Power consumption1 W
Channels2
Number of programs90
Program typesWeekly and daily programs
Operating modesManual, automatic, holiday
Time tolerance≤1 s/day at 25°C
Power reserve10 years
DisplayBacklighted LCD
Number of contacts2 C/O
Contact rating16 A / 250 V AC1
Switching capacity4000 VA AC1, 384 W DC
Rated insulation voltage250 V
Permissible relative humidity≤50% at 40°C without condensation
Ambient temperature-20°C to 55°C
Storage temperature-30°C to 70°C
Wire size1-4 mm
Tightening torque0.5 Nm
MountingTH-35 rail (EN 60715)
Dimensions90 x 36 x 64 mm
Pollution degree3
Protection degreeIP20
Altitude≤2000 m
Maximum pilotable power2300 W, 2300 W, 1000 W, 500 W, 500 W

Frequently asked questions

How many programs can the EDT-PD2 store?

It can store 90 programs.

What is the power reserve of the real-time clock?

The internal battery provides a 10-year power reserve.

How do I reset the device to factory settings?

Press the four keys simultaneously for 0.5 seconds.

What is the pulse output duration range?

The pulse duration can be set from 1 to 99 seconds.

Download PDF (1.8 MB)

Also Manuals