This guide shows how to connect a Winbest DP‑Modbus converter between a Siemens S7‑300 PLC and a seven‑segment display using USB debugging and DP‑Modbus…
The document describes the hardware wiring of a Winbest DP‑Modbus converter, a Siemens S7‑300 PLC (CPU313C‑2DP) and a customer‑provided seven‑segment display. It includes a connection diagram, USB debugging setup, and the steps to read the display manual for required Modbus commands.
It then explains how to configure the DP‑Modbus module in STEP7: downloading and installing the D_MASTER.GSD file, setting the DP address and baud rate, mapping Modbus registers (address 1, start register 144), and writing PLC data to the display registers. The guide finishes with a sample PLC program and verification of the displayed value (4.90). This manual is written in Chinese.
| USB debugging interface | Yes |
|---|---|
| Supported baud rate | 187.5 Kbps |
| DP address setting | Hardware DIP switches (1‑8) |
Connect the module’s USB port to the PC, install the USB driver, then use a serial‑assistant program or ModbusPoll to send and monitor Modbus commands.
Download the D_MASTER.GSD file from Winbest’s website and copy it to the Step7\S7data\gsd\ directory.