R. STAHL 8252/1 Explosion-Proof Junction Box User Manual

The 8252/1 series of junction boxes is an explosion-proof device approved for use in Zones 1, 2 and 21, 22. They are used to distribute electrical power in areas where there is a risk of explosion.


R. STAHL 8252/1 Explosion-Proof Junction Box User Manual - cover page
Brand
R. STAHL
Category
Other products
Document type
User Manual
Language
Chinese
Pages
13
File format
PDF
File size
1.3 MB
Published
07 November, 2023
Updated
07 November, 2023
MD5 checksum
086A907A466CBFECBE7B077CB864FDA8

About this manual

This document is the Chinese user manual for the R. STAHL 8252/1 explosion-proof junction box. It covers intended use, technical data, transport and storage, dimensions, assembly, installation conditions, wiring, commissioning, maintenance, accessories and disposal.

The junction box is an explosion-protected device approved for zones 1, 2, 21 and 22 and is used to distribute electrical energy in hazardous areas. It has an IP66 enclosure, an ambient temperature range of -60 to +70 °C and a maximum rated voltage of 690 V, depending on the components installed inside. This manual is written in Chinese.

What's inside

  • General information
  • Symbols used
  • General safety instructions
  • Intended use
  • Special versions
  • Technical data
  • Transport and storage
  • Installation
  • Dimensions and mounting dimensions
  • Assembly and disassembly

Specifications

Explosion protection (IECEx)IECEx BVS 11.0059X Ex d [ia/ib Ga/Gb] IIC T4 ... T6 Gb; Ex tb IIIC T80 °C ... T130 °C Db; IP66
Explosion protection (ATEX)BVS 11 ATEX E 114 X E II 2 G Ex d [ia/ib Ga/Gb] IIC T4 ... T6 Gb; E II 2 D Ex tb IIIC T80 °C ... T130 °C Db; IP66
CertificationsIECEx, ATEX, India (PESO), Kazakhstan (TR), Russia (TR), Belarus (TR)
Rated voltageUp to 690 V, depending on installed components
Rated currentUp to 175 A, depending on installed components
Connection cross-sectionUp to 70 mm², depending on installed components
Housing materialAluminum cast alloy, copper-free, powder coated, color RAL 7032
Protective conductor connectionM6 grounding bolt, inside and outside the housing
Tightening torque2.8 Nm for the protective conductor connection bolt
Protection ratingIP66 according to IEC/EN 60529
Maximum thread sizeM25, M32, M40 or M63 metric, or 3/4 in, 1 in, 1-1/4 in or 2 in NPT, depending on size

Frequently asked questions

What is the R. STAHL 8252/1 junction box used for?

It is an explosion-protected junction box approved for zones 1, 2, 21 and 22, used to distribute electrical energy in hazardous areas.

What protection rating does the enclosure have?

The enclosure has protection rating IP66 according to IEC/EN 60529.

What tightening torque is specified for the protective conductor connection bolt?

The protective conductor connection bolt tightening torque is 2.8 Nm.

Download PDF (1.3 MB)