The SDHG-185 relay protection test instrument is a multifunctional instrument specially designed for testing current transformer volt-ampere characteristics, ratio and polarity discrimination. It can also be used for transformer polarity discrimination testing.
This is the Chinese user manual (使用说明书) for the Sudian Electric SDHG-185 volt-ampere characteristic, ratio and polarity comprehensive tester, a multifunction test instrument designed for relay protection work on current transformers. It can also be used for polarity testing of transformers. The instrument uses a microprocessor for data acquisition, analysis and storage, has a built-in micro printer for test data and curves, and automatically calculates the CT ratio, so one person can complete the full test.
The manual explains the technical parameters, the panel layout and the numbered controls, and gives step-by-step wiring and operating procedures for the volt-ampere characteristic test, the ratio test and the polarity test, plus safety precautions such as grounding the device and making sure the CT secondary has no ground point. Rated weight is 23 kg and dimensions are 470 × 340 × 260 mm. This manual is written in Chinese.
| Input voltage | AC 220 V or 380 V, 50 Hz, input voltage detected automatically |
|---|---|
| Output voltage | 0–500 V with 220 V input; 0–1000 V with 380 V input |
| Maximum instantaneous current (ratio test) | 600 A |
| Volt-ampere characteristic test current | 15 A |
| Digital voltmeter range | 0–9999 V, resolution 0.1 V |
| Digital ammeter range | 0–3000 A, resolution 0.01 A |
| Accuracy | Current ≤ 1 %, voltage ≤ 1 % |
| Storage capacity | 20 sets of current and voltage values with curve |
| Operating temperature | 0 ~ 40 °C |
| Dimensions | 470 × 340 × 260 mm |
| Weight | 23 kg |
It is designed for relay protection testing of current transformers: volt-ampere characteristics, ratio measurement and polarity discrimination. It can also be used for polarity testing of transformers.
AC 220 V or 380 V, 50 Hz, with automatic recognition of the input voltage. When 380 V is needed for output above 500 V, the manual says to input 380 V.
Up to 20 sets of current and voltage values can be stored and then printed together with the volt-ampere characteristic curve.
The current transformer secondary winding must have no ground point, wiring changes may only be made with the regulator and output switches off, and the device must be reliably grounded before the test.