The Hui dian four-channel current and voltage acquisition module is a high-precision, high-reliability data acquisition module. It can collect AC voltage, AC current, apparent power, active power and other parameters. The module uses the MODBUS-RTU communication protocol to communicate with the上位机.
This manual covers the Hui dian HD450VXXA4TH series four-channel current and voltage acquisition module, including its precautions, parameter list, MODBUS-RTU communication protocol, and register map.
The module measures AC current and voltage on four channels and communicates over RS485 using MODBUS-RTU, with specifications such as a 50 A current range, 450 V voltage range, and default 9600,N,8,1 communication. This manual is written in Chinese.
| Power supply voltage | DC 8-28 V (with self-recovering fuse) |
|---|---|
| Rated power | 3 W |
| AC voltage measurement error | Typical ±1% @50 Hz |
| AC current measurement error | Typical ±1% @50 Hz |
| Apparent power measurement error | Typical ±2% @50 Hz |
| Active power measurement error | Typical ±4% @50 Hz |
| AC voltage resolution | 0.60 V (450 V range) |
| AC current resolution | 0.04 A (50 A range) |
| Data refresh frequency | >5 Hz |
| Communication interface | RS485 with isolation and TVS protection |
| Operating temperature | -20 to 50 °C |
| Operating humidity | 5% to 90%, non-condensing |
| Operating altitude | Below 2000 m |
| Rated frequency | 50 Hz |
| Default communication baud rate | 9600, N, 8, 1 |
| Maximum network nodes | 32 |
| Current range | 50 A |
| Voltage range | 450 V |
| Number of channels | 4 (A, B, C, D) |
The default baud rate is 9600, N, 8, 1.
A maximum of 32 nodes can be on the same network.
The warranty is valid for one year from the purchase date; human damage is not covered.
All current channel registers use 0.002 A units.