Hui dian HD450VXXA4TH Series Four-Channel Current and Voltage Acquisition Module V2.1 Product Manual

The Hui dian four-channel current and voltage acquisition module is a high-precision, high-reliability data acquisition module. It can collect AC voltage, AC current, apparent power, active power and other parameters. The module uses the MODBUS-RTU communication protocol to communicate with the上位机.


Hui dian HD450VXXA4TH Series Four-Channel Current and Voltage Acquisition Module V2.1 Product Manual - cover page
Brand
Hui Dian
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
3
File format
PDF
File size
638 KB
Published
07 November, 2023
Updated
07 November, 2023
MD5 checksum
820562ABADB5050D103E71AF9F3F6C41

About this manual

This manual covers the Hui dian HD450VXXA4TH series four-channel current and voltage acquisition module, including its precautions, parameter list, MODBUS-RTU communication protocol, and register map.

The module measures AC current and voltage on four channels and communicates over RS485 using MODBUS-RTU, with specifications such as a 50 A current range, 450 V voltage range, and default 9600,N,8,1 communication. This manual is written in Chinese.

What's inside

  • Precautions
  • Parameter list
  • MODBUS-RTU communication protocol
  • MODBUS registers
  • Notes

Specifications

Power supply voltageDC 8-28 V (with self-recovering fuse)
Rated power3 W
AC voltage measurement errorTypical ±1% @50 Hz
AC current measurement errorTypical ±1% @50 Hz
Apparent power measurement errorTypical ±2% @50 Hz
Active power measurement errorTypical ±4% @50 Hz
AC voltage resolution0.60 V (450 V range)
AC current resolution0.04 A (50 A range)
Data refresh frequency>5 Hz
Communication interfaceRS485 with isolation and TVS protection
Operating temperature-20 to 50 °C
Operating humidity5% to 90%, non-condensing
Operating altitudeBelow 2000 m
Rated frequency50 Hz
Default communication baud rate9600, N, 8, 1
Maximum network nodes32
Current range50 A
Voltage range450 V
Number of channels4 (A, B, C, D)

Frequently asked questions

What is the default MODBUS communication setting?

The default baud rate is 9600, N, 8, 1.

How many devices can share one network?

A maximum of 32 nodes can be on the same network.

What is the warranty period?

The warranty is valid for one year from the purchase date; human damage is not covered.

What happens if register 0005H current multiplier is set to 500?

All current channel registers use 0.002 A units.