This document describes the features and functions of the 2V68-S series relays.
The 2V68-S is a three phase monitoring device designed to provide continuous supervision of the CT summation circuit in high impedance type protection schemes. It detects open circuited CT wiring and open circuited main current transformers, and provides latching alarm and CT shorting contacts.
This guide describes the relay's operator interface, scheme wiring, settings, and commissioning. It also covers voltage setting dials, optional time delay, power and flag indicators, terminal layout, dimensions, and connection diagrams.
| Voltage setting range | 2-14 V AC per phase |
|---|---|
| Continuous rating | 300 V RMS |
| Alarm output contacts | 3 latching N/O |
| CT shorting contacts | 3 latching N/O |
| Operate time delay | 3 seconds fixed; optional 3-20 seconds adjustable |
| Harmonic filter | Rejects 2nd, 3rd, 4th and 5th harmonics |
| Terminals | M4 screw terminals |
| Mounting | Flush panel mounted or 4U high 19 inch rack frame |
It is a three phase monitoring device designed to provide continuous supervision of the CT summation circuit in high impedance type protection schemes.
The adjustable voltage setting for each phase ranges from 2 to 14 V AC.
It provides three latching normally open alarm output contacts.
The module may be either flush panel mounted or mounted on a 4U high 19 inch rack frame.