ISO 10 module provides galvanic isolation between the input and output signals and supply voltage. ISO 10 can also be used as a signal converter and amplifier between wide ranges of signal options. Galvanic isolation may be needed if the system has multiple grounding points. Potential difference between the grounding points causes loop currents, which may interfere with the transferred signal. ISO 10 breaks the ground loop current path.
Produal ISO 10 (product number 1182060) is a galvanic isolator and signal converter. The document states that the ISO 10 module provides galvanic isolation between the input and output signals and the supply voltage, and that it can also be used as a signal converter and amplifier between wide ranges of signal options. Isolation may be needed when a system has multiple grounding points, because the potential difference between the grounding points causes loop currents that can interfere with the transferred signal; the ISO 10 breaks the ground loop current path.
The module is supplied with 24 Vac (22…28 V) or 24 Vdc (24…28 V), consumes less than 2 VA and has an isolation voltage below 500 Vdc. Input voltage ranges are 0…1 V, 0…10 V and 2…10 V at 100 kΩ impedance, current inputs are 0…20 mA and 4…20 mA, and the outputs are 0/2…10 V or 0/4…20 mA. Connection is made with 5-pin plug-in terminals on the bottom (terminals 1–5) and top (terminals 6–10) of the 18 x 114 x 80 mm IP20 housing.
| Supply | 24 Vac (22…28 V) / 24 Vdc (24…28 V) |
|---|---|
| Power consumption | < 2 VA |
| Isolation voltage | < 500 Vdc |
| Input voltage | 0…1 V / 0…10 V / 2…10 V, impedance 100 kΩ |
| Input current | 0…20 mA / 4…20 mA |
| Output voltage | 0/2…10 V, load +2 mA / -0,5 mA |
| Output current | 0/4…20 mA, loop resistance max. 500 Ω |
| Deviation | < 0,35 % FSO (25 °C) |
| Response time | about 1 s |
| Ambient temperature | 0…50 °C |
| Protection class | IP20 |
| Dimensions (w x h x d) | 18 x 114 x 80 mm |
| Transmitter supply (+V terminal) | 15 Vdc / 20 mA max., referenced to input side ground |
It is supplied with 24 Vac (22…28 V) or 24 Vdc (24…28 V) and consumes less than 2 VA.
It provides galvanic isolation between the input and output signals and the supply voltage, and can also be used as a signal converter and amplifier between wide ranges of signal options.
Supply and input are on the bottom connector (1–5) and supply and output on the top connector (6–10); the 5-pin plug-in terminals help connecting the device.
Yes, an external 2-wire transmitter can be supplied from the +V terminal with max. 15 V / 20 mA, referenced to input side ground.