Produal ISO 10 Galvanic Isolator / Signal Converter Datasheet

ISO 10 module provides galvanic isolation between the input and output signals and supply voltage. ISO 10 can also be used as a signal converter and amplifier between wide ranges of signal options. Galvanic isolation may be needed if the system has multiple grounding points. Potential difference between the grounding points causes loop currents, which may interfere with the transferred signal. ISO 10 breaks the ground loop current path.


Produal ISO 10 Galvanic Isolator / Signal Converter Datasheet - cover page
Brand
Produal
Category
Converter
Document type
Datasheet
Language
English
Pages
1
File format
PDF
File size
254 KB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
BE90C00AA548B2F438E26AF06F293B13

About this manual

Produal ISO 10 (product number 1182060) is a galvanic isolator and signal converter. The document states that the ISO 10 module provides galvanic isolation between the input and output signals and the supply voltage, and that it can also be used as a signal converter and amplifier between wide ranges of signal options. Isolation may be needed when a system has multiple grounding points, because the potential difference between the grounding points causes loop currents that can interfere with the transferred signal; the ISO 10 breaks the ground loop current path.

The module is supplied with 24 Vac (22…28 V) or 24 Vdc (24…28 V), consumes less than 2 VA and has an isolation voltage below 500 Vdc. Input voltage ranges are 0…1 V, 0…10 V and 2…10 V at 100 kΩ impedance, current inputs are 0…20 mA and 4…20 mA, and the outputs are 0/2…10 V or 0/4…20 mA. Connection is made with 5-pin plug-in terminals on the bottom (terminals 1–5) and top (terminals 6–10) of the 18 x 114 x 80 mm IP20 housing.

What's inside

  • Technical data
  • Wiring
  • Input and output signal range selection
  • Wiring example 1: Signal isolation
  • Wiring example 2: Signal isolation/conversion
  • Ordering guide

Specifications

Supply24 Vac (22…28 V) / 24 Vdc (24…28 V)
Power consumption< 2 VA
Isolation voltage< 500 Vdc
Input voltage0…1 V / 0…10 V / 2…10 V, impedance 100 kΩ
Input current0…20 mA / 4…20 mA
Output voltage0/2…10 V, load +2 mA / -0,5 mA
Output current0/4…20 mA, loop resistance max. 500 Ω
Deviation< 0,35 % FSO (25 °C)
Response timeabout 1 s
Ambient temperature0…50 °C
Protection classIP20
Dimensions (w x h x d)18 x 114 x 80 mm
Transmitter supply (+V terminal)15 Vdc / 20 mA max., referenced to input side ground

Frequently asked questions

What supply voltage does the Produal ISO 10 need?

It is supplied with 24 Vac (22…28 V) or 24 Vdc (24…28 V) and consumes less than 2 VA.

What is the ISO 10 used for?

It provides galvanic isolation between the input and output signals and the supply voltage, and can also be used as a signal converter and amplifier between wide ranges of signal options.

How are the terminals arranged on the ISO 10?

Supply and input are on the bottom connector (1–5) and supply and output on the top connector (6–10); the 5-pin plug-in terminals help connecting the device.

Can an external transmitter be powered from the ISO 10?

Yes, an external 2-wire transmitter can be supplied from the +V terminal with max. 15 V / 20 mA, referenced to input side ground.

Download PDF (254 KB)