Produal TEK NTC 10 Duct Temperature Sensor Datasheet

Produal TEK NTC 10 duct temperature sensor with a 10 kΩ NTC thermistor, IP54 housing, -50...70 °C range and ±0.2 °C accuracy at 25 °C.


Produal TEK NTC 10 Duct Temperature Sensor Datasheet - cover page
Brand
Produal
Category
Temperature sensors
Document type
Datasheet
Language
English
Pages
1
File format
PDF
File size
46 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
1B4F5757E0C0714D5214D5EE526FE4BF

About this manual

The Produal TEK NTC 10 is a duct temperature sensor intended for automatic ventilating systems. It uses a 10 kΩ NTC thermistor at 25 °C and is mounted to the duct with an adjustable connection flange. Installation depth can be adjusted between about 100 and 220 mm, and the screw cover and terminal blocks tilted to 45° are intended to make installation easy.

Technical data lists a stem of ∅ 8 mm x 220 mm, a plastic housing rated for below 120 °C, protection class IP 54 with cable entry or stem down, and an M16 cable entry. The measuring range is -50...70 °C with accuracy of ±0.2 °C at 25 °C. The product fulfills the requirements of directive 2004/108/EY and is in accordance with EN61000-6-3:2001 (Emission) and EN61000-6-2:2001 (Immunity). The ordering guide lists model TEK NTC 10, product number 1175040.

What's inside

  • Duct temperature sensor
  • Technical data
  • Temperature/Resistance
  • Installation
  • Ordering guide

Specifications

Sensor10 kΩ NTC thermistor
Nominal resistance10 kΩ / 25 °C
Stem∅ 8 mm x 220 mm
HousingPlastic (< 120 °C)
Protection classIP 54, cable entry or stem down
Cable entryM16
Measuring range-50...70 °C
Accuracy± 0.2 °C at 25 °C
Installation depthca 100...220 mm
Product number1175040
Directive2004/108/EY

Frequently asked questions

What is the TEK NTC 10 used for?

It is a duct temperature sensor designed for automatic ventilating systems to detect duct temperature.

What is the sensor's nominal resistance?

The NTC thermistor has a nominal resistance of 10 kΩ at 25 °C.

What temperature range does the sensor cover?

-50...70 °C.

What is the accuracy at 25 °C?

±0.2 °C.