This document is a product manual for residual current operated circuit breakers, which introduces the features and characteristics of the product.
This product manual is issued by the Bureau of Indian Standards as reference material for Regional/Branch Offices and licensees under Scheme-I of the BIS (Conformity Assessment) Regulations, 2018. It covers Residual Current Operated Circuit Breakers Without Integral Overcurrent Protection for Household and Similar Uses (RCCBs) according to IS 12640(Part 1):2016/IEC 61008-1:2012, and may also be used by prospective applicants seeking a BIS certification licence.
The document states the product standard and its four amendments, sampling guidelines including a sample size of 15, and the scope of the licence. Annex A lists the major test equipment with the clause references of the tests it is used for, Annex B gives the scheme of inspection and testing with Table 1 of test details and levels of control (routine tests, test sequences A to J, frequencies and sub-contracting rules), and Annex C lists the tests possible in a day.
| Product standard | IS 12640(Part 1):2016/IEC 61008-1:2012 |
|---|---|
| Number of amendments | 4 |
| Sample size | 15 Nos. |
| Product covered | Residual Current Operated Circuit Breakers Without Integral Overcurrent Protection for Household & Similar Uses (RCCB) |
| Grouping guideline | Each and every rating of RCCB is to be tested for GOL and Inclusion |
The sampling guidelines give a sample size of 15 Nos.
The product shall meet IS 12640(Part 1):2016/IEC 61008-1:2012, which has four amendments.
The tripping test (D.2) is a routine test carried out on each piece, and RCCBs that fail a routine test shall not be marked.
All the RCCBs of the same fundamental design manufactured in a shift shall constitute a control unit.