Ulke ULDW-5A Earth Ground Resistance Tester User Manual

ULDW-5A Earth Ground Resistance Tester is a product suitable for testing the ac grounding resistance, contact voltage, step voltage, etc. of various grounding devices and soil resistivity.


Ulke ULDW-5A Earth Ground Resistance Tester User Manual - cover page
Brand
优利克电力
Category
Test Set
Document type
User Manual
Language
Chinese
Pages
15
File format
PDF
File size
652 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
126A7F8B34DC58BF34AC9D4F4BFF5CD6

About this manual

The Ulke ULDW-5A is a ground resistance tester that uses a variable-frequency AC source and microcomputer control. The manual says it is intended to measure power-frequency grounding impedance, contact voltage, step voltage, equivalent power-frequency parameters and soil resistivity, and that it can measure without interrupting power.

The manual describes the instrument's principles, panel, measurement wiring and operating steps. The tester uses 45 Hz and 55 Hz for variable-frequency measurement and has a maximum output current of 5 A; its grounding impedance range is 0 to 200 Ω and its soil resistivity range is 0 to 1000 Ω·m. This manual is written in Chinese.

What's inside

  • Instrument Overview
  • Performance Features
  • Technical Specifications
  • Instrument Principle
  • Panel Introduction
  • Measurement Wiring
  • Operating Steps
  • Menu Description
  • Troubleshooting
  • Accessories List

Specifications

Grounding Impedance Range0 to 200 Ω (including current stake impedance)
Grounding Impedance Resolution0.001 Ω
Grounding Impedance Error±(reading × 1% + 0.005 Ω)
Maximum Output VoltageAC 400 V (45 Hz/55 Hz dual-frequency sine wave)
Maximum Output CurrentAC 5 A (45 Hz/55 Hz dual-frequency sine wave)
Current Output Ranges5/4.5/4/3.5/3/2.5/2/1.5/1 A, 0.5 A per step, 9 ranges
Interference ResistanceWithstands 10 V at power frequency 50 Hz
Supply PowerAC 220 V ±10%, 50 Hz
Dimensions (W × D × H)295 × 340 × 310 mm
Weight30 kg
Soil Resistivity Range0 to 1000 Ω·m
Soil Resistivity Resolution0.01 Ω·m

Frequently asked questions

What measurement frequencies does the ULDW-5A use?

In variable-frequency mode it uses 45 Hz and 55 Hz; in fixed-frequency mode it uses a strict 50 Hz.

What is the maximum output current of the tester?

The maximum output current is AC 5 A, using 45 Hz and 55 Hz dual-frequency sine wave output.

Can the ULDW-5A be used without interrupting the power supply?

Yes. The text states that it can measure without a power outage because of its anti-interference capability.

How long does the tester's automatic check usually take?

The automatic checks normally take about 15 seconds.

Download PDF (652 KB)