This manual introduces the operation and maintenance instructions of EAHU control cabinet, including: overall switch, control panel, indicator light, operation, remote equipment start confirmation, filter check, etc.
This is the Chinese-language operation and maintenance manual, document DTR-CG-ver. 1.4 (02.2009), for VTS control cabinets VS 21-150 CG 0-1, VS 180-300 CG 0-1 and VS 400-650 CG 0-1. The cabinets are used in ventilation systems to control exhaust air handling units (EAHU) equipped with VTS-standard frequency inverters. The manual is split into a user part covering the main switch, control panel, indicator lights and operation, and an advanced part for detailed control description.
The advanced part describes the VTS-E-0006 electronic module, output control of the exhaust unit through the inverters 2U1 to 2U4, the local, remote and CO-detector control channels, the external start permission (ESP) signal, fire and inverter alarm inputs, control logic diagrams, damper control, filter check with differential pressure switches, wiring requirements and the technical data of the cabinet. Safety notes warn that the external control circuit at terminals X3 stays live when the main switch is off, and that fire alarm or inverter fault stops the exhaust unit and must be reset with main switch Q1. This manual is written in Chinese.
| Weight | 5.3 kg |
|---|---|
| Dimensions | 460 x 340 x 170 mm |
| Rated supply voltage U3 | 3×400 V or 1×230 V |
| Rated insulation voltage Ui | 400 V |
| Rated impulse withstand voltage Uimp | 2.5 kV |
| Rated short-circuit current | 6 kA |
| Rated frequency | 50 Hz ± 1 Hz |
| Protection degree | IP54 |
| Permitted operating temperature | 0 to 50 °C |
| Control circuit supply voltage | 24 V AC |
| Fuse F11 (CO detector supply circuit) | 5x20 mm T 1.25 A |
| Fuse F13 (main module circuit) | 5x20 mm F 800 mA |
| START CONFIRMATION contact rating | 24 V AC/DC, 2 A |
The cabinet must be fed from the main switchboard with 3×400 V/50 Hz or 1×230 V/50 Hz; the control circuit itself runs on 24 V AC.
After the fault is cleared, switch the main switch Q1 off and on again to reset the fault memory of the control module.
The exhaust unit runs at maximum speed to force fast air exchange and reduce the risk from harmful gas.
The passive relay contact is rated 24 V AC/DC at 2 A and is taken to terminals X3:22 to X3:24.