VTS VS 21-150 / 180-300 / 400-650 CG 0-1 EAHU Control Cabinet Operation and Maintenance Manual
This is the Chinese-language operation and maintenance manual, document DTR-CG-ver. 1.4 (02.2009), for VTS control cabinets VS 21-150 CG 0-1, VS 180-300 CG 0-1 and VS 400-650 CG 0-1. The cabinets are used in ventilation systems to control exhaust air handling units (EAHU) equipped with VTS-standard frequency inverters. The manual is split into a user part covering the main switch, control panel, indicator lights and operation, and an advanced part for detailed control description.
The advanced part describes the VTS-E-0006 electronic module, output control of the exhaust unit through the inverters 2U1 to 2U4, the local, remote and CO-detector control channels, the external start permission (ESP) signal, fire and inverter alarm inputs, control logic diagrams, damper control, filter check with differential pressure switches, wiring requirements and the technical data of the cabinet. Safety notes warn that the external control circuit at terminals X3 stays live when the main switch is off, and that fire alarm or inverter fault stops the exhaust unit and must be reset with main switch Q1. This manual is written in Chinese.
Covers: 控制说明 · 总开关 · 控制面板与指示灯说明 · 运行 · 排风机组输出控制 · 排风机组启动控制信号
Latest VTS manuals
VTS VS 21-150 / 180-300 / 400-650 CG 0-1 EAHU Control Cabinet Operation and Maintenance Manual
User Manual 14 pages · 1.6 MB · ZHVTS operation and maintenance manual (DTR-CG-ver. 1.4) for VS 21-150, VS 180-300 and VS 400-650 CG 0-1 control cabinets used to control exhaust air handling…
Which document do I need?
User Manual
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in VTS manuals
What supply voltage does the EAHU control cabinet need?
The cabinet must be fed from the main switchboard with 3×400 V/50 Hz or 1×230 V/50 Hz; the control circuit itself runs on 24 V AC.
From: VTS VS 21-150 / 180-300 / 400-650 CG 0-1 EAHU Control Cabinet Operation and Maintenance Manual
How is the alarm reset after a fire alarm or inverter fault?
After the fault is cleared, switch the main switch Q1 off and on again to reset the fault memory of the control module.
From: VTS VS 21-150 / 180-300 / 400-650 CG 0-1 EAHU Control Cabinet Operation and Maintenance Manual