Instruction manual of ARD series three-phase elevator emergency self-rescue device, introduces the product's model, specification, appearance size, wiring, operation and maintenance.
This Chinese-language user manual, version V1.1, describes the three-phase ARD Series elevator power-failure self-rescue device. It explains the model code for the 3P normal type and 3T heavy-duty type, the nameplate, standard specifications, model selection tables and the two enclosure sizes.
The manual also covers wiring for ARD3PXX and ARD3TXX systems, the working principle, the operation panel with four LEDs, a four-digit display and two switches, fault codes E.01 to E.13, and battery replacement using ARD3P15A as an example. This manual is written in Chinese.
| Product types | 3P normal type and 3T heavy-duty type |
|---|---|
| Recommended elevator self-rescue speed | 1/12 of the rated running speed |
| Single run time | 5 min |
| Output voltage waveform | Sine wave |
| Cooling method | Forced air cooling |
| Protection rating | IP20 |
| Ambient temperature and humidity | -15 to 40 °C; 90%RH or less, non-condensing, well ventilated |
| ARD3P15A input | AC 3PH 340–420 V, 50/60 Hz |
| ARD3P15A output | AC 1PH 380 V, 50/60 Hz, 1.5 A (1.0 kVA) |
The main contactor opens, the elevator system is disconnected from the external supply, and the device produces three-phase AC 380 V in about 15 s to put the elevator into self-rescue operation.
It can run for a maximum of 5 minutes per operation and then automatically cuts off.
E.01 is battery undervoltage; possible causes are insufficient battery charging time, end of battery life, or an abnormal charging circuit.
The recommended elevator self-rescue speed is 1/12 of the elevator rated running speed.