This is a user manual for EMCP II+ and EMCP II+P control panels, which mainly introduces the composition and functions of the control panels
This service manual excerpt covers the Caterpillar EMCP II+ and EMCP II+P control panels used on generator sets. It identifies panel-mounted and internal components, including the GSC+/GSC+P, CAM, ALM, switches, relays, fuses, terminal blocks, and customer connection points, with reference illustrations.
The text also gives engine starting and stopping procedures using the Engine Control Switch, governor switch or speed potentiometer, and voltage adjust rheostat. It includes notes on emergency shutdown, resetting the emergency stop button, and resetting the air shutoff if equipped. This manual is written in Chinese.
| Control panel models | EMCP II+ and EMCP II+P |
|---|---|
| Emergency stop button color | Red |
| Low idle speed (60 Hz units) | Approximately 2/3 of full load speed |
| Low idle speed (50 Hz units) | Approximately 4/5 of full load speed |
| Low idle cool-down time | Approximately five minutes |
Turn the Engine Control Switch (ECS) to the Manual Start position. The engine will start and run as long as the ECS stays in that position.
Remove the load, then turn the Engine Control Switch to the Stop position. The engine will run for the preset or programmed cool-down time before shutting down.
Correct the problem that required the emergency stop, then reset the button by pulling out and rotating it in the direction shown. If equipped, reset the air shutoff as well.
Most components are in the front panel, mounting plate, customer connection box (3412), or wiring box.