T6861 series digital liquid crystal display thermostat is a temperature controller for two-pipe and four-pipe fan coil control, with automatic/manual three-speed fan control, water valve control, ventilation mode and other functions.
The T6861 series large-screen LCD thermostat is described in this data sheet (document APH07CH04 - R2001CN) for 110/220 VAC two-pipe and four-pipe fan-coil control. Basic models cover two-pipe and four-pipe single-cooling, single-heating and manual heating/cooling changeover, with ventilation mode, automatic or manual three-speed fan control, water valve control, timer on/off, timer cycle (CPH), energy-saving mode via dry contact or key press, keypad lock, and an optional external temperature sensor. Horizontal and vertical versions are available with blue or green backlight and matching trim, and the unit mounts directly on an 86×86 mm junction box.
The document explains valve control, fan operation and the four-pipe automatic changeover dead band, temperature display, backlight, external sensor and operating modes (comfort, ventilation, energy saving, freeze protection). It also gives technical specifications, terminal designations, wiring diagrams for two-pipe heating-only, two-pipe cooling-only, two-pipe manual changeover and four-pipe applications, plus mounting, installer setup (ISU) and installation test procedures. This manual is written in Chinese.
| Operating frequency | 50/60 Hz |
|---|---|
| Control method | PI control algorithm, on/off control |
| Protection class | IP20 |
| Mounting | Directly on a wall-mounted 86×86 mm junction box or a 2×4 inch junction box |
| Backlight duration | 8 seconds after the last key press; 60 seconds in installer setup and test modes |
| Timer setting step | 0.5 hour |
| Display | Large display with English text and icons |
| Freeze protection | When enabled and the thermostat is off, heating starts below 6 °C room temperature and runs until 8 °C is reached |
It takes the temperature from its built-in or an external sensor and switches a control valve open or closed so the room temperature stays at the setpoint.
Yes. Besides the built-in sensor, temperature control can use an external T7770A1006 (NTC20K) sensor.
Through a passive dry contact such as a hotel room key card, or by pressing and holding the mode key; the setpoint then changes to the configured energy-saving heating or cooling value.
When it is enabled and the thermostat is off, heating is started if the room falls below 6 °C and continues until 8 °C is reached or the thermostat is switched on.