eSelect M1 CD COOL Cooling Water Treatment Controller Operating Instructions and Maintenance Manual

This is the operating instructions and maintenance manual for eSelect M 1 CD COOL


eSelect M1 CD COOL Cooling Water Treatment Controller Operating Instructions and Maintenance Manual - cover page
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
36
File format
PDF
File size
2.7 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
8D9A0385BC2B8DA5D738F8F3601E7F78

About this manual

This manual covers the eSelect M1 CD COOL, a multi-purpose single-parameter instrument intended for measurements in cooling towers and designed for cooling water treatment, air purifier and humidifier abatement, or any industrial conditioning system. The controller can interact with conductivity sensors chosen by measurement range, flow meters and drain solenoid valves, and it offers two purge operation modes, four inhibitor metering modes and control of two biocide metering pumps.

The document first gives warnings, symbols, transport and handling notes and intended use, then describes assembly, wall installation and the diagram of electrical connections. Later sections explain the control panel and display, ON-OFF mode, MIN/MAX alarm, hysteresis, setpoint delay, 4-20 mA analogue outputs, real-time timers, the flow sensor function, Ethernet/RS485 communication with an external module, the purge, inhibitor and biocide menus, probe calibration and settings, ending with sensor cleaning, maintenance, technical specifications and troubleshooting.

What's inside

  • Warnings and symbols used in the manual
  • Transport and handling
  • Intended use of the device
  • Assembly and disassembly of the instrument
  • Wall installation
  • Diagram of electrical connections
  • Control Panel and description of the display
  • ON-OFF mode, MIN/MAX alarm, hysteresis and delay on setpoint
  • Analogue 4-20 mA outputs
  • Purge menu and purge operations

Specifications

Power supply100/240 VAC, 50/60 Hz single-phase (12/24 V on demand)
Consumption5 W at 240 VAC
Case materialABS plastic
DisplayBacklit 126x64, visible area 70x37 mm
Conductivity range, K1up to 20.00 mS, resolution 10 µS
Conductivity range, K5up to 2,000 µS, resolution 1 µS
Temperature probe range-20 ... 100 °C
Relay output rating5 A max at 230 Vac, voltage-free
Analogue outputs0/4...20 mA1 and 0/4...20 mA2, 500 ohm maximum input impedance
Relay insulation voltage>3000 Vac
Warranty1 year, excluding parts subject to normal wear

Frequently asked questions

What is the eSelect M1 CD COOL used for?

It is a multi-purpose single-parameter instrument for measurements in cooling towers, designed for cooling water treatment, air purifier and humidifier abatement, or any industrial conditioning system.

What power supply does the instrument require?

A 100/240 VAC, 50/60 Hz single-phase supply, with maximum fluctuations of ±10% permitted; 12/24 V is available on demand.

Which temperature sensor does it use?

A PT100 temperature sensor, with manual or automatic offset; the probe range is -20 to 100 °C.

How long is the warranty?

One year, excluding parts subject to normal wear such as valves, fittings, pipe clamps, tubes, filter and injection valve.

Download PDF (2.7 MB)