This manual introduces the characteristics and parameter setting methods of Voltage Protection Relay, suitable for single-phase and three-phase power grids, and can realize overvoltage, undervoltage, voltage imbalance, phase reversal, neutral line break and phase failure protection
The Rishabh voltage protection relay is described as protecting a system from undervoltage, overvoltage, phase unbalance, phase failure, incorrect phase sequence, and neutral disconnection. Front adjustment knobs set nominal voltage, system type, trip delay, and fault trip points; LEDs indicate the fault type, and potential-free relay contacts can switch a load or trigger an alarm. The device has fail-safe operation, and all faults are self-resetting.
The manual gives parameter settings, installation requirements, dimensions and mounting details, connection diagrams, terminal assignments, tripping diagrams, adjustment and LED indication tables, and technical specifications. It covers 1-phase, 3-phase 3-wire, and 3-phase 4-wire connections, DIN-rail or wall mounting, and a test certificate.
| Overvoltage trip point | 105-125% (variable) |
|---|---|
| Undervoltage trip point | 75-95% (variable) |
| Voltage unbalance trip point | 20% (fixed) |
| Phase failure trip point | 70% (fixed) |
| Trip delay | 0-10 seconds variable for undervoltage, overvoltage, and unbalance |
| Power-on delay | Approx. 3 seconds (fixed) |
| Operating temperature | -10 to +55°C |
| Storage temperature | -25 to +70°C |
| Relative humidity | 0...90% non condensing |
| Dimensions | 18 x 90 x 66 mm |
| Mounting | Standard 35 mm DIN rail (DIN50022) |
| Housing | 17.5 mm standard housing suitable for DIN-rail or wall mount |
| Contact rating | 5A/250V AC/30VDC (resistive load) |
| Accuracy | ±3% of nominal value |
| Response time | <200 msec |
| Nominal frequency | 50/60 Hz |
It protects against under voltage, over voltage, phase unbalance, phase failure, incorrect phase sequence, and neutral disconnection faults.
Yes. The overvoltage and undervoltage faults can be disabled, but the other faults cannot be disabled.
The trip delay is adjustable from 0 to 10 seconds for undervoltage, overvoltage, and unbalance.
The device has a 17.5 mm housing suitable for DIN-rail or wall mounting.