PAM Drinking Water and Sewage Piping Systems Installation Guide

This file is an installation guide for piping systems, including pipes, fittings, supports, etc.


PAM Drinking Water and Sewage Piping Systems Installation Guide - cover page
Brand
PAM
Category
Other
Document type
Installation Guide
Language
English
Pages
60
File format
PDF
File size
16.1 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
8777208CA5A9B1DCF83C8B9CA93CCA22

About this manual

This installation guide covers drinking water and sewage systems, from storage and handling of pipes, fittings and accessories through assembly of the different joint types. It gives stacking heights, bundle weights and pipe unit weights for diameters from DN 60 to DN 2000, together with lifting methods for bundles and single pipes.

Joint assembly steps are described for the Blutop, Blutop Vi, Topaz, Topaz Vi, Standard, Standard Vi, ViLoK, Express, Universal, TAG, IM and flanged joints, including cleaning, gasket insertion, lubrication, chamfering and depth checks. Later sections cover assembly equipment, pipe cutting, locking weld bead, anchor blocks, hydraulic testing, external coating and internal lining repairs, repair products, polyethylene sleeve, ovality correction, dismantling joints, repairing pipes, branches for sewage pipes and video tutorials. The contractor is responsible for analyzing and eliminating risks during installation.

What's inside

  • Storage
  • Handling
  • Blutop / Blutop Vi / Topaz / Topaz Vi joint
  • Standard joint / Standard Vi / ViLoK joint
  • Express joint
  • Universal Vi joint / Universal Ve joint
  • TAG / IM joint
  • Flanged joint
  • Assembly equipment
  • Pipe cutting

Specifications

Storage life of EPDM gaskets (drinking water systems)10 years in optimal storage conditions
Storage life of other gaskets7 years in optimal storage conditions
Gasket material for drinking waterEPDM
Gasket material for sewageNBR with yellow marking
Joint lubricantBlutop lubricant paste (ref. 214616)
Diameter range delivered in bundlesDN 60 to 300
Diameter range delivered looseDN 350 to 2000
Angular deflection of joint+6° / -6°

Frequently asked questions

What should be done with rings when installing pipes at low temperatures?

Bring rings up to a temperature of 20°C to ensure maximum flexibility, for example by immersing them in warm water.

Which lubricant is used on the inserted gasket and the spigot?

They must be lubricated with Blutop lubricant paste (ref. 214616).

How can I check the joint depth after assembly?

After assembly, only a single line should still be visible.

When may the joint be deflected?

Only when it is fully assembled and before the system is pressurized.