This is an installation manual that describes how to install the TOTAL GROUND system.
This manual provides instructions for installing TOTAL GROUND grounding and lightning protection systems. It covers system inspection, storage, soil preparation, and the construction of the electrode pit. The guide details the installation of the electrode, including the use of H2Ohm soil conditioner, and the connection of admittance couplers. This manual is written in Spanish.
| Maximum vertical distance between electrode and coupler (grounding system) | 85m |
|---|---|
| Maximum distance between electrode and coupler (lightning protection system) | 10m |
| Maximum distance from coupler to lightning rod tip | 235m |
| Maximum resistance for the grounding system | 2 Ohms |
The manual recommends using the H2Ohm soil conditioner to achieve low and permanent resistance.
You need to add 20 liters of water for each bag of H2Ohm compound used.
The angle of change in direction of the cabling must not be less than 45°.