Sterling and Wilson Solar Inverter Transformers for PV Power Plants Generic Guidelines
The paper presents generic guidelines for selecting inverter transformers used at the output of inverters in utility-scale photovoltaic plants. It describes terminology, recommends sizing the transformer according to the inverter reference load cycle and correlating it with temperature rise in line with IEC 60076-7, and discusses PCB-free mineral oil, dielectric breakdown voltage, and component and unit codes and standards.
It also explains magnetizing inrush and the effects of harmonics on transformer heating and insulation life. For harmonic currents above 5% of rated current, it says the heating effect should be evaluated using IEEE C57.110-1998.
Covers: Introduction · Terminology & Selection · Transformer Oil · What is PCB · Dielectric Breakdown Voltage (BdV) · Standard for testing mineral oil
Latest Sterling and Wilson Solar manuals
Sterling and Wilson Solar Inverter Transformers for PV Power Plants Generic Guidelines
Other 9 pages · 6.8 MB · ENGeneric guidelines from Sterling and Wilson Solar on selecting inverter transformers for utility-scale PV power plants, covering oil, standards and harmonics.
Questions answered in Sterling and Wilson Solar manuals
What oil is recommended for inverter transformers?
The recommended oil is PCB free, polycyclic, aromatic, hydrocarbon free mineral oil in line with IEC 60296.
From: Sterling and Wilson Solar Inverter Transformers for PV Power Plants Generic Guidelines
How often should in-service transformer oil be tested?
For in-service equipment, it is recommended to test the oil at least once a year.