This is an operating manual for SBK TwinCo 3000 distribution station
The SBK TwinCo 3000 is a heating circuit distribution station for underfloor heating, made up of a flow distributor and a return distributor and supplemented by a control valve and a pump. It is operated with the SBK Tempus digital controller, which controls the flow temperature either by outside temperature, by boiler flow temperature or as a fixed value controller.
The operating guide covers the station's technical data, its thermal function, the electrical connection of the Tempus control, the available operating modes and control knob settings, the heating curve diagrams for outside-temperature and boiler-temperature controlled operation, and mistake removal. The electrical connection must be made by a qualified electrician.
| Suitable floor surface output | max. 1,200 l/h (approx. 28,800 kJ) with completely open throttle valve |
|---|---|
| Preliminary heat temperature, heating system | min +70 °C |
| Preliminary heat temperature, floor | +20 °C to +50 °C |
| Middle temperature difference | 6 to 8 K and approx. 75 W/m² |
| Pump | Wilo RS 25/6-3, 3 speed steps (46/67/93 W), IP 42, max. 34 dB(A) |
| Pump speed area | 1,100 - 2,200 1/min |
| Regulator connection voltage | 230 V ~, 50 Hz, 1.5 VA, IP 42 |
| Regulator ambient conditions | -20 °C to +50 °C |
| Safety temperature limiter switch-off | floor preliminary heat temperature above 60 °C |
The system automatically switches into the constant flow temperature mode.
It switches off the complete arrangement at a floor preliminary heat temperature above 60 °C.
The valves open and close slowly, in steps of approximately 5 minutes.
Control knob C is used to set the required flow temperature; knobs A and B have no function in this mode.