This document is about the serial communication manual of REVO CL, introduces the serial communication protocol and function of REVO CL
This manual describes serial communication for the CD Automation REVO CL thyristor unit. It covers the RS485 port, MODBUS RTU protocol restrictions, message format, supported functions, exception responses and address configuration.
The manual also lists parameter addresses and values for average voltage, current, power, status, command, setpoint, output, current limit, firing mode, feedback, burst firing, delay triggering, soft start, proportional band and integral time. It includes a C language CRC16 example.
| Communication port | Two-wire RS485, half-duplex |
|---|---|
| Baud rate | 4800, 9600 or 19200 Baud (standard 19200) |
| Transmission format | 1 start bit, 8 data bits, 1 stop bit |
| Parity | None |
| Device address range | 1 (default) to 127 |
| Network capacity | Up to 127 REVO M units |
| Read Holding Registers limit | Maximum 13 parameters per message |
| Preset Multiple Registers limit | One parameter per message |
It uses MODBUS RTU over a two-wire RS485 port.
The baud rate can be 4800, 9600 or 19200 Baud; 19200 is the standard.
It is set from 1 (default) to 127 using parameter P115 in the Hardware menu.
No; globally addressed queries receive no response.