TEMPERATURE CONTROLLER N322T OPERATING MANUAL - V1.8x H The N322T is a 2-output digital electronic controller for heating and cooling applications. It is available with NTC thermistor input sensor, Pt100 or J/K/T type thermocouple. Sensor offset correction is provided. The 2 independent outputs can be used as control or alarm. Displays the Compressor Protection Function by Supply Voltage Monitoring, important in the protection of compressors for refrigeration systems.
The N322T is a 2-output digital electronic controller for heating and cooling applications. It is available with NTC thermistor, Pt100, or J/K/T thermocouple input sensors, and provides sensor offset correction. Its two independent outputs can be used as control or alarm, and it displays a compressor protection function by supply voltage monitoring.
This manual covers specifications, electrical wiring, and operation. Configuration is organized into levels for temperature measurement, setpoint adjustment, configuration, and calibration, with parameters for units, input type, offsets, limits, hysteresis, alarms, control action, and timing.
| Input sensor options | NTC thermistor, Pt100, or J/K/T thermocouple |
|---|---|
| Sensor offset correction | Provided |
| Outputs | 2 independent outputs usable as control or alarm |
| Compressor protection | Displayed by supply voltage monitoring |
| NTC thermistor resistance | 10 kΩ at 25 °C |
| NTC temperature range | -50 to 120 °C (-58 to 248 °F) |
| NTC accuracy | 0.6 °C (1.1 °F) |
| NTC interchangeability error | 0.75 °C (1.35 °F) |
| NTC operating range | -30 to +105 °C (-222 to +221 °F) |
| NTC cable length | 3 m |
| NTC cable extension | Up to 200 m |
| Pt100 temperature range | -50 to 300 °C (-58 to 572 °F) |
| Pt100 temperature coefficient | α = 0.00385 |
| Pt100 accuracy | 0.7 °C (1.3 °F) |
| Thermocouple J range | 0 to 600 °C (32 to 1112 °F) |
| Thermocouple K range | -50 to 1000 °C (-58 to 1832 °F) |
| Thermocouple T range | -50 to 400 °C (-58 to 752 °F) |
| Thermocouple accuracy | 3 °C (5.4 °F) |
| Measurement resolution | 0.1° from -19.9 to 199.9°, 1° elsewhere |
| Output 1 | Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A resistive) |
| Output 1 optional pulse | Pulse, 5 Vdc, 25 mA max |
| Output 2 | Relay 3 A / 250 Vac, SPST-NA |
| Power supply voltage | 100~240 Vac/dc (±10%) |
| Optional power supply | 24 V (12~30 Vdc/ac) |
| Mains frequency | 50~60 Hz |
| Power consumption | 5 VA |
| Dimensions | 75 x 33 x 75 mm |
| Weight | 100 g |
| Panel cut-out | 70 x 29 mm |
| Operating temperature | 0 to 40 °C (32 to 104 °F) |
| Storage temperature | -20 to 60 °C (-4 to 140 °F) |
| Relative humidity | 20 to 85 % (non-condensing) |
| Housing | Polycarbonate UL94 V-2 |
| Protection degree | Front panel IP65, box IP42 |
| Suitable wiring | Up to 4.0 mm² |
| Communication | RS-485, RTU MODBUS protocol (optional) |
| Serial interface isolation | Not isolated from input circuitry |
| Serial interface isolation (24 V model) | Isolated from input circuitry except in 24 V powered model |
It can use an NTC thermistor, Pt100, or J/K/T type thermocouple.
The standard supply is 100~240 Vac/dc (±10%), with an optional 24 V (12~30 Vdc/ac) supply.
Press for 1 second until the SP message appears.
It displays the compressor protection function by supply voltage monitoring.