This is an instruction manual, which introduces the SCHRACK URNA0345's usage method
The Schrack URNA0345 is a multinational grid and system protection unit that protects energy generation plants such as combined heat and power plants, wind generators, waterpower plants and photovoltaic plants. It disconnects power generating plants from the mains supply during power failures or grid anomalies to avoid unintentional feeding to the grid.
This Quick Start Guide covers safety information, intended use, controls, terminals, technical data, mounting, available configurations and local standards, connection diagrams and menu structure. It does not replace the full operation manual, which is available from the manufacturer's website.
| Supply voltage | DC: 24 V; AC: 110-230 V |
|---|---|
| Supply voltage tolerance | DC: ±10%; AC: ±30% |
| Nominal consumption | max. 1.25 W / 4 VA @ 230 V AC |
| Rated frequency | 50 / 60 Hz |
| Measuring input | 3 x 400 V AC |
| Input impedance | 1 MΩ |
| Line to line voltage range | 0-560 V AC |
| Line to neutral voltage range | 0-325 V AC |
| Frequency range | 40-65 Hz |
| RoCoF range | 100 mHz/s to 2000 mHz/s |
| Phase shift range | 1-15° |
| Number of relay contacts | 3 changeover contacts |
| Rated current | 5 A / 250 V AC |
| Ambient temperature, operation | -25 to +55 °C |
| Weight | 300 g |
It is a multinational grid and system protection unit that protects energy generation plants such as combined heat and power plants, wind generators, waterpower plants and photovoltaic plants.
It supports DC 24 V and AC 110-230 V.
It has three changeover contacts.
The measuring input is 3 x 400 V AC.