NF Level Probe User Manual introduces the features and characteristics of the magnetic level probes produced by North American Eagle Energy Corporation and their usage instructions
This user manual covers the NF level probe family from North Falcon Energy: the NF RDT intrinsically safe magnetostrictive level probe radio data transmitter and the intrinsically safe fuel probes NF 485, NF TTL, NF 420, NF 010 and NF PLM. It gives the device description, electrical characteristics for each type, product marking, probe dimensions, on-tank installation rules, wired connections, wireless setting, maintenance and device return. The probes are intended to be installed by trained service engineers.
The sensor consists of a probe head and a stainless steel probe tube fitted in the tank with a screw-in unit for height adjustment. It operates on the magnetostrictive measuring principle, using a float for product filling level and an additional float for continuous water detection. The devices must be powered through an intrinsically safe barrier, for example North Falcon models ISB-PC or ISB-PR, and the sensor and floats are maintenance free when operated to the manufacturer's specifications.
| Measurement range | 200 mm to 12,500 mm |
|---|---|
| Maximum mechanical length | 13,000 mm |
| Measurement accuracy | +/- 0.5 mm |
| Measurement resolution | +/- 0.05 mm |
| Temperature accuracy | +/- 0.2 °C |
| Housing protection | IP68, stainless steel case |
| Probe shaft material | Stainless steel AISI 304 / 316 |
| Supply voltage (NF 485, NF PLM) | 12 Vdc nominal, 30 V max, through an intrinsically safe barrier |
| NF RDT battery | 3.6 Vdc intrinsically safe lithium battery, SAFT LS33600 or EVE ER34615 |
| NF RDT battery life | Up to 3 years (standard setting) |
| NF RDT transmission frequency | 169 MHz |
| NF RDT transmission power | Up to 200 mW |
| Maximum transmission distance | Up to 2 km based on the RS485 interface standard |
| Operating temperature | -40 °C to +85 °C |
| NF 420 output | 4 to 20 mA, 2 wires, 1 product float |
| NF 010 output | 0 to 10 Vdc, 4 wires, 1 product float |
| Approvals | OIML-R85 for fixed applications |
It is the radio frequency version of the intrinsically safe magnetostrictive level probe. It is powered by an intrinsically safe lithium battery and transmits with up to 200 mW at 169 MHz.
Yes, the magnetostrictive probe can be installed in hazardous areas. The device must be powered and connected with an intrinsically safe barrier such as North Falcon model ISB-PC or ISB-PR, or an equivalent intrinsically safe device.
For products with a density greater than 0.9 kg/l, water detection cannot take place and the water float must be removed.